Every answer on this page applies only to the W-BACnet Compact (SKU 840-2230, BACnet MS/TP). Do not use these answers for other LumenRadio products or form factors. Full manual: W-BACnet Compact manual

Product overview

W-BACnet Compact (840-2230): What is W-BACnet Compact and what does it do?

Also asked as:

W-BACnet replaces the RS485 control cable in a BACnet MS/TP installation with a wireless mesh link, removing daisy-chaining and cable planning while keeping standard BACnet MS/TP compatibility. The Compact works only as a mesh Node, connected to a BACnet MS/TP server; the Gateway, connected to the BACnet MS/TP client, must be a Wall mount or DIN rail unit.

Manual section: Introduction > Product Overview (section ID: product-overview)

W-BACnet Compact (840-2230): How many devices can a W-BACnet network support?

Also asked as:

Up to 100 mesh nodes per gateway, and up to 50 BACnet MS/TP devices on the gateway's RS485 bus (1 on a Compact node). For fast, stable control the manual recommends no more than 25 BACnet MS/TP devices per wireless network; split larger systems into several networks.

Manual section: Introduction > Product Overview; Application Guide > Best Practice Settings (section ID: product-overview)

W-BACnet Compact (840-2230): Is there a PRO version of the Compact?

Also asked as:

No. The Compact has no PRO variant. PRO versions, which support up to 4 connected local BACnet MS/TP devices when used as a mesh node (versus 1 on the standard units), are only available for the DIN rail and Wall mount form factors.

Manual section: Introduction > Glossary of Terms (section ID: glossary-of-terms)

W-BACnet Compact (840-2230): What is the difference between a Gateway and a Node?

Also asked as:

The Gateway is the single root device of the network, connected to the BACnet MS/TP client; all unicast traffic passes through it. Nodes connect to BACnet MS/TP servers, and every node also acts as a repeater automatically, even with no device connected. Use only one gateway per network. DIN rail and Wall mount units can be gateways; any form factor can be a node.

Manual section: Glossary of Terms; System Description > W-BACnet Mesh Network; Radio planning > Gateway & Node selection (section ID: gateway-node-selection)

Safety

W-BACnet Compact (840-2230): What safety precautions apply when installing the device?

Also asked as:

Disconnect power before wiring, verify the supply matches spec and check DC polarity, use correctly rated wiring and overcurrent protection, follow local electrical codes, use ESD protection, and have only qualified technicians install it. Do not install in wet locations or above 95% RH, do not use if damaged, and do not use for safety-critical tasks.

Manual section: Safety Information; Warnings and Precautions (section ID: safety-information)

W-BACnet Compact (840-2230): What should I watch out for when sharing a power supply with other devices?

Also asked as:

All power connections must share the same polarity: the W-BACnet "+" terminal must never connect to the "–" terminal of another device, especially where other devices are half-wave rectified. Wrong polarity can damage the unit, the supply, or other connected devices.

Manual section: Safety Information > Power and RS485 Circuit Caution (section ID: power-and-rs485-circuit-caution)

Specifications

W-BACnet Compact (840-2230): What are the power requirements?

Also asked as:

24 VAC ±10% or 12–24 VDC ±10%. Maximum consumption is 0.8 W (average 0.45 W). Troubleshooting guidance asks for a supply that can deliver at least 0.5 A.

Manual section: Device Overview > Specifications; Troubleshooting > None of the LEDs are blinking (section ID: specifications)

W-BACnet Compact (840-2230): What are the physical and environmental specs of the Compact unit?

Also asked as:

48 × 85 × 22 mm, 55 g, IP40, internal antenna. Operating temperature −20 °C to +55 °C (−4 °F to 131 °F), storage −30 °C to +80 °C, humidity 10–95% non-condensing. Terminals accept 0.2–1.5 mm² conductors (AWG 24–16).

Manual section: Device Overview > Specifications (section ID: specifications)

W-BACnet Compact (840-2230): What radio frequency and output power does it use?

Also asked as:

2402–2480 MHz (2.4 GHz band) with maximum RF output power of 100 mW. Network traffic is encrypted with AES-128 using credentials unique to each gateway.

Manual section: Device Overview > Specifications; System Description > W-BACnet Mesh Network (section ID: specifications)

W-BACnet Compact (840-2230): Does the Compact have a termination resistor, and can I disable it?

Also asked as:

Yes, it has a built-in 120 Ω end-of-line resistor that cannot be disabled. Place the unit at one end of the RS485 trunk and terminate the other end with a 120 Ω resistor (built-in or external).

Manual section: Setup Guide > Wiring > Wiring Diagram; Troubleshooting > Can the EOL resistor be disabled? (section ID: wiring-diagram)

Device overview

W-BACnet Compact (840-2230): What are the physical components on the device?

Also asked as:

From the device overview: LEDs, push button, power connector, RS485 bus connector and a knockout for cable entry. The Compact has no DIP switches, no three-pole mode switch and no antenna connector.

Manual section: Device Overview (section ID: device-overview)

System

W-BACnet Compact (840-2230): What is the difference between commissioning mode and secure mode?

Also asked as:

Commissioning mode uses known, shared credentials so new nodes can find and join a gateway. When the gateway is switched to secure mode, all nodes reboot together and switch to encrypted credentials unique to that gateway for long-term operation, so nearby networks don't interfere.

Manual section: System Description > Commissioning Network / Secure Network (section ID: commissioning-network)

W-BACnet Compact (840-2230): What is autobaud, and is it enabled on the Compact?

Also asked as:

Autobaud automatically detects the bus baud rate, and it is enabled by default on the Compact (there are no DIP switches). The device cycles through 115200, 76800, 57600, 38400, 19200 and 9600 (FW 4.0.0+) and locks on once the local device has put more than three valid messages on the bus. If it fails, the Compact tries the gateway's settings for a while and then retries autobaud. Double-press the button to retry manually.

Manual section: System Description > Autobaud (section ID: autobaud-automatic-baudrate-detection)

W-BACnet Compact (840-2230): How do I turn off autobaud on Compact devices?

Also asked as:

The Compact has no DIP switches, but when both the gateway and the Compact devices run firmware 4.3.1 or later, the gateway can force autobaud off for all Compact devices in the network. Press the button on the gateway five times; the middle LED on the gateway blinks red to confirm. While autobaud is forced off, the Compact devices use the bus settings distributed by the gateway. To allow autobaud again, press the gateway button five times again; the middle LED blinks green to confirm. DIN rail and Wall mount devices are not affected; their autobaud is controlled by DIP switch 4.

Manual section: System Description > Autobaud > Forcing Autobaud Off on Compact Devices (section ID: forcing-autobaud-off-on-compact-devices)

W-BACnet Compact (840-2230): How does the gateway share its serial settings with nodes?

Also asked as:

The gateway distributes its bus settings (e.g., baud rate) to all nodes. The Compact always tries autobaud first and falls back to the gateway's configuration if autobaud can't find the baud rate. This means different baud rates can be mixed in one system.

Manual section: System Description > Config Distribution; Setup Guide > Set the baud rate on the Gateway (section ID: config-distribution)

W-BACnet Compact (840-2230): What is FOTA and do I need to update every node?

Also asked as:

Firmware-Over-The-Air (from FW 3.0.0) lets the gateway push new firmware to every node in a secure network automatically. Update only the gateway, preferably through the W-BACnet app; propagation typically takes 30 minutes to 2 hours depending on network size. Progress is shown via FOTA Status in the app. If the devices run firmware below 3.0.0, FOTA is not available and they must be updated using the nRF Connect update flow.

Manual section: System Description > FOTA; Mobile App > Complete update / FOTA status (section ID: firmware-over-the-air-fota)

Accessories

W-BACnet Compact (840-2230): Are there accessories for the Compact?

Also asked as:

The Compact manual lists no accessories. The Compact has an internal antenna only and no antenna connector. If you need an external antenna, an outdoor kit or installation in a metal enclosure, use a DIN rail unit instead.

Manual section: Device Overview > Specifications; Radio planning > Wireless design considerations (section ID: specifications)

W-BACnet Compact (840-2230): How do I install W-BACnet outdoors?

Also asked as:

Place the device inside a suitably rated IP enclosure (the Compact itself is IP40). Do not use a metal enclosure with the Compact: in metal-case installations the manual says to use a DIN rail version with its antenna mounted outside the enclosure. Mount it where snow can't cover it.

Manual section: Radio planning > Outdoor Installations; Radio planning > Radiation pattern > Compact (section ID: outdoor-installations)

See also: Radiation pattern (section ID: radiation-pattern), Wireless best practices (section ID: installation-and-placement-of-wireless-devices-and-external-antennas)

W-BACnet Compact (840-2230): Can I use an external or third-party antenna?

Also asked as:

No. The Compact has an internal antenna and no antenna connector; only the DIN rail supports external antennas. If you need an external antenna, use a DIN rail unit.

Manual section: Device Overview > Specifications; Radio planning > Wireless design considerations (section ID: specifications)

W-BACnet Compact (840-2230): Which antenna setup should I choose?

Also asked as:

The Compact has a fixed internal antenna, so there are no antenna options. Place it in open space with a clear path to neighboring nodes, at least 1.5 m (5 ft) above the floor and not inside a metal cabinet or enclosure. The antenna selector options in the manual apply to the DIN rail only. For the best performance, physically install the unit according to the radiation pattern shown in the images in Radio planning > Radiation pattern (section ID: radiation-pattern).

Manual section: Device Overview > Specifications; Radio planning; Radio planning > Radiation pattern > Compact (section ID: specifications)

See also: Radiation pattern (section ID: radiation-pattern), Wireless best practices (section ID: installation-and-placement-of-wireless-devices-and-external-antennas)

W-BACnet Compact (840-2230): What range can I expect with each antenna?

Also asked as:

The manual's range table covers the DIN rail and its antenna options only (e.g., 1.8 dBi kit ~450 m / 1500 ft, 6 dBi directional ~600 m / 2000 ft, DIN rail in a metal enclosure ~15 m / 50 ft); it gives no figure for the Compact. Real-world range depends on walls, metal and other obstructions, so use the app's range test to check a link. Do not install the Compact inside a metal cabinet or enclosure.

Manual section: Radio planning > Antenna Range estimates; Mobile App > Range Test Mode; Radio planning > Radiation pattern > Compact (section ID: antenna-range-estimates)

See also: Radiation pattern (section ID: radiation-pattern), Wireless best practices (section ID: installation-and-placement-of-wireless-devices-and-external-antennas)

W-BACnet Compact (840-2230): Can I swap or fit an external antenna?

Also asked as:

No. The Compact's antenna is internal and cannot be swapped. If you need an external antenna, use a DIN rail unit.

Manual section: Device Overview > Specifications; Radio planning > Radiation pattern > Compact (section ID: specifications)

See also: Radiation pattern (section ID: radiation-pattern), Wireless best practices (section ID: installation-and-placement-of-wireless-devices-and-external-antennas)

LEDs

W-BACnet Compact (840-2230): What do the LED patterns mean?

Also asked as:

Blue sweep = node in commissioning mode; green sweep = gateway in commissioning mode; all blink green = network found; all blink yellow = restarting; first LED green/yellow/red = node signal strength; first LED blinking yellow = node connecting; all solid red = firmware error (contact support); all blink white = identify. Read the LEDs left to right.

Manual section: LED Status Indicators > LED Pattern Descriptions (section ID: led-pattern-descriptions)

W-BACnet Compact (840-2230): What does the third (RS485) LED tell me?

Also asked as:

It blinks green (1 s on, 4 s off) when an RS485 device is found and red when none is found. A faster red blink (0.5 s on/off) means autobaud is running.

Manual section: LED Status Indicators > LED Pattern Descriptions (section ID: led-pattern-descriptions)

W-BACnet Compact (840-2230): Why did the LEDs turn off?

Also asked as:

LEDs switch off after 30 minutes by default. A single press extends them by 30 minutes; holding the button 5 s (release on magenta) sets them to always on. Since FW 4.2.1 LEDs stay on if an issue is being indicated.

Manual section: LED Status Indicators; Button Functionality (section ID: led-status-indicators)

Button

W-BACnet Compact (840-2230): What does each button press do?

Also asked as:

Single press: keeps the LEDs on for 30 more minutes. Double press: retries autobaud. Triple press: Bluetooth/app mode for 3 minutes (middle LED flashes blue twice). Five presses (DIN rail or Wall mount gateway only; gateway and Compacts need FW 4.3.1+): toggles forcing autobaud off for all Compact devices in the network (middle LED blinks red = forced off, green = allowed). Hold and release on color: 5 s magenta = LEDs always on; 10 s blue = uncommission; 15 s cyan = show firmware version; 20 s red = firmware update (bootloader) mode.

Manual section: Button Functionality (section ID: button-functionality)

W-BACnet Compact (840-2230): How do I factory-reset / uncommission a node?

Also asked as:

Hold the button for 10 seconds and release when the middle LED shows blue. The device returns to commissioning mode (blue sweep) ready to join a new network. Nodes can also be removed via the app's commissioning screen.

Manual section: Button Functionality > Held button behavior; Mobile App > Removing Commissioned Devices (section ID: held-button-behavior)

Mobile app

W-BACnet Compact (840-2230): What can the W-BACnet mobile app do and what do I need?

Also asked as:

Update firmware, diagnose the network (network map, PDR, range test, diagnostics), show device information, commission nodes and replace gateways. You need Bluetooth on, the device powered and within range, and internet access to download firmware. Triple-press the device button to make it connectable for 3 minutes.

Manual section: Mobile App > Features / Requirements / Device Connection (section ID: mobile-app)

W-BACnet Compact (840-2230): How do I read the network map?

Also asked as:

It shows a tree of the gateway and its nodes (children indented under parents). The hexagon left of each name shows PDR: green ≥ 99%, amber 94–99%, red < 94%. The RS485 hexagon is green if a local device is connected (red if not), with the BACnet MS/TP addresses shown bottom-left. Use Identify (LEDs blink white) and Rename (ASCII, max 8 characters).

Manual section: Mobile App > Network Map (section ID: network-map-overview)

W-BACnet Compact (840-2230): Why are some PDR values missing in the network map?

Also asked as:

Nodes may not yet have calculated and sent a PDR to the gateway, or they run firmware older than 3.0.0, which only shows limited information.

Manual section: Mobile App > Network Map > Missing PDR values (section ID: missing-pdr-values)

W-BACnet Compact (840-2230): How do I generate a network map PDF report and why should I?

Also asked as:

Connect to the gateway, open the network map, select Generate PDF report, optionally add company and installer names, then save or share. Always keep it: it contains the recovery information required to replace a gateway, and support asks for it.

Manual section: Mobile App > PDF Report Generation; Gateway Replacement (section ID: pdf-report-generation)

W-BACnet Compact (840-2230): How do I run a range test?

Also asked as:

Requires FW 4.2.1+ and a commissioned network. In the app, connect to the gateway > Settings > Range Test > toggle on, then do the same on the node. LED 1 shows PDR and LED 3 latency (green good, yellow fair, red weak). BACnet MS/TP traffic is blocked during the test; disable it on both node and gateway afterwards (auto-exits after 30 min from FW 4.3.0).

Manual section: Mobile App > Range Test Mode; Release Notes 4.3.0 (section ID: range-test-mode)

W-BACnet Compact (840-2230): How do I get diagnostics from a device for support?

Also asked as:

Connect to the device in the app, tap the Settings icon, choose Diagnostics, then tap Get Diagnostics.

Manual section: Mobile App > Device Diagnostics (section ID: how-to-retrieve-diagnostics)

W-BACnet Compact (840-2230): How do I install beta firmware?

Also asked as:

When the app starts, tap the LumenRadio logo 8 times and select Beta mode. "Beta Mode" appears in red in the top-right corner.

Manual section: Mobile App > Switching Update Channel (section ID: switching-update-channel)

W-BACnet Compact (840-2230): The app firmware update failed. What should I do?

Also asked as:

Make sure the device is in range and connected; if it still fails, restart both the app and the W-BACnet device and try again. The W-BACnet app is always the preferred update method. If the update still fails after multiple attempts with the W-BACnet app, use the nRF Connect update flow as a fallback (this flow is also required for devices running firmware below 3.0.0).

Manual section: Mobile App > Mobile App Troubleshooting (section ID: mobile-app-troubleshooting)

Gateway replacement

W-BACnet Compact (840-2230): How do I replace a broken gateway without recommissioning?

Also asked as:

The gateway is always a Wall mount or DIN rail unit (the Compact can't be a gateway), so this applies to that unit; Compact nodes don't need recommissioning. Use Gateway Replacement in the app (Settings > Gateway Replacement). You must have the recovery info from a previously saved Network Map PDF (import the PDF, scan its QR code, or type the 32 recovery numbers). Power off the old gateway permanently, power on the new one, triple-press it, select and identify it in the app to complete. Without saved recovery info, recovery isn't possible.

Manual section: Mobile App > Gateway Replacement (section ID: gateway-replacement)

Radio planning

W-BACnet Compact (840-2230): Where should I place devices and antennas for best signal?

Also asked as:

Keep ~3/4 inch clearance around the antenna, mount at least 1.5 m (5 ft) above the floor, never install the Compact inside a metal cabinet or enclosure, keep it clear of surrounding metal, and keep outdoor antennas clear of snow. Avoid bottleneck nodes and add repeaters for long or obstructed paths; bring a spare unit to use as a repeater. For the best performance, physically install the unit according to the radiation pattern shown in the images in Radio planning > Radiation pattern (section ID: radiation-pattern).

Manual section: Radio planning > Wireless design considerations / Installation Guidelines; Radio planning > Radiation pattern > Compact (section ID: installation-and-placement-of-wireless-devices-and-external-antennas)

See also: Radiation pattern (section ID: radiation-pattern)

W-BACnet Compact (840-2230): Can I install the Compact inside a metal electrical cabinet?

Also asked as:

No. The Compact must not be installed inside a metal electrical cabinet or enclosure. Metal severely attenuates the radio signal, which drastically reduces range and link quality. Mount the Compact outside the cabinet, ideally in open space with a clear path to neighboring nodes. If the connected device sits inside a cabinet, run the RS485 cable out to the Compact. Where the unit must be housed inside a metal cabinet, use the DIN rail form factor with an external antenna mounted outside the enclosure. For the best performance, physically install the unit according to the radiation pattern shown in the images in Radio planning > Radiation pattern (section ID: radiation-pattern).

Manual section: Radio planning > Electrical Cabinets; Antenna Range estimates; Radio planning > Radiation pattern > Compact (section ID: electrical-cabinets)

See also: Radiation pattern (section ID: radiation-pattern), Wireless best practices (section ID: installation-and-placement-of-wireless-devices-and-external-antennas)

W-BACnet Compact (840-2230): How should I position the units to get the best wireless performance?

Also asked as:

Physically install the units according to the radiation pattern shown in the images in Radio planning > Radiation pattern (section ID: radiation-pattern); this gives the best wireless performance. Placement is especially important for the Compact: do not install it inside a metal cabinet or enclosure, because the metal severely attenuates the radio signal strength. Mount it in open space, at least 1.5 m (5 ft) above the floor, with a clear path to neighboring nodes.

Manual section: Radio planning > Radiation pattern (section ID: radiation-pattern)

See also: Electrical Cabinets (section ID: electrical-cabinets)

Setup

W-BACnet Compact (840-2230): What do I need before installation?

Also asked as:

Disconnect power, check BACnet MS/TP requirements (Application Guide) and environment (wireless design). Use shielded twisted-pair RS485 cable with 100–130 Ω impedance. Compact-specific: minimal space is needed, but ensure proper ventilation and allow for the cable bend radius. Follow local codes and use PPE. Do not install the Compact inside a metal cabinet or enclosure: the metal attenuates the wireless signal and drastically reduces range. Mount it outside the cabinet and, if the connected device is inside, run the RS485 cable out to it. See Electrical Cabinets (section ID: electrical-cabinets).

Manual section: Setup Guide > Pre-installation Requirements; Radio planning > Radiation pattern > Compact (section ID: pre-installation-requirements)

See also: Radiation pattern (section ID: radiation-pattern), Wireless best practices (section ID: installation-and-placement-of-wireless-devices-and-external-antennas)

W-BACnet Compact (840-2230): What are the physical installation steps?

Also asked as:

1) Check the unit for damage. 2) Mount the backplate of the enclosure on the wall; it fits onto a junction box. 3) Connect power and the BACnet MS/TP device, using the rear and/or side knockouts for cable entry. 4) Confirm the wiring is secure and the LEDs light. 5) Secure the front case to the backplate. The Compact detects the baud rate with autobaud and falls back to the gateway's settings. Do not install the Compact inside a metal cabinet or enclosure: the metal attenuates the wireless signal and drastically reduces range. Mount it outside the cabinet and, if the connected device is inside, run the RS485 cable out to it. See Electrical Cabinets (section ID: electrical-cabinets).

Manual section: Setup Guide > Physical Setup; Radio planning > Radiation pattern > Compact (section ID: physical-setup)

See also: Radiation pattern (section ID: radiation-pattern), Wireless best practices (section ID: installation-and-placement-of-wireless-devices-and-external-antennas)

W-BACnet Compact (840-2230): Where should I install the Compact? Can it go inside a metal cabinet?

Also asked as:

Install the Compact outside any metal cabinet or enclosure, ideally in open space with a clear path to neighboring nodes. Do not place it inside a metal cabinet: the metal attenuates the wireless signal and drastically reduces range and link quality. If the connected device sits inside a cabinet, run the RS485 cable out to the Compact. If the unit must be housed inside a metal cabinet, use the DIN rail form factor with an external antenna mounted outside the cabinet. For the best performance, physically install the unit according to the radiation pattern shown in the images in Radio planning > Radiation pattern (section ID: radiation-pattern).

Manual section: Radio planning > Electrical Cabinets (section ID: electrical-cabinets)

W-BACnet Compact (840-2230): Should I commission with the app or without it?

Also asked as:

There are two valid ways to commission a Compact node to a gateway: the mobile app commissioning method and the physical commissioning method (without the app). Both work, but the mobile app method is preferred: it identifies devices, adds nodes and shows the network map. The Compact works only as a node, so the gateway is always a Wall mount or DIN rail unit, and the gateway's three-pole switch sets the network mode (the Compact has no switch). With the app, the gateway stays in secure mode (switch in the secure-gateway position). With the physical method, set the gateway switch to the commissioning position (COMM. on a DIN rail, ◻ on a Wall mount), let the Compact and other nodes join, then switch it back to the secure-gateway position. To add nodes to an existing network, use the app; putting the gateway back into commissioning mode uncommissions all existing nodes.

Manual section: Setup Guide > Commissioning procedure selector (section ID: commissioning-procedure-selector)

W-BACnet Compact (840-2230): How do I commission nodes using the mobile app?

Also asked as:

This is the preferred of the two valid commissioning methods (the other is the physical commissioning method, without the app). The Compact works only as a node, so it joins a Wall mount or DIN rail gateway. Set the gateway's three-pole switch to the secure-gateway position (Gateway on a DIN rail, ◼ on a Wall mount). Triple-press the gateway button, open the app, tap Commission, then identify and select (and optionally rename) the gateway. The Compact ships in commissioning mode (blue sweep); if it doesn't show a blue sweep, hold its button for 10 s to uncommission it. Tap Add on the Compact; it reboots and its first LED turns green, yellow or red to show signal strength. Check the node count and network map afterwards.

Manual section: Mobile App Commissioning Method (Step-by-Step) (section ID: mobile-app-commissioning-method-stepbystep)

W-BACnet Compact (840-2230): How do I commission without the app?

Also asked as:

This is the physical commissioning method, one of two valid ways to commission nodes; the other is the mobile app method, which is preferred. The Compact works only as a node and has no switch, so all mode changes are made on the gateway (a Wall mount or DIN rail unit). Set the gateway's three-pole switch to the commissioning position (COMM. on a DIN rail, ◻ on a Wall mount). Power the Compact: it shows a blue sweep in commissioning mode (if not, hold its button for 10 s). The Compact blinks all LEDs green when it receives the network credentials. Confirm all devices in your BACnet MS/TP controller, then set the gateway switch back to the secure-gateway position (Gateway on a DIN rail, ◼ on a Wall mount); the nodes blink yellow and reboot. The network takes up to 15 minutes to reform.

Manual section: Physical Commissioning Method (Step-by-Step) (section ID: physical-commissioning-method-stepbystep)

W-BACnet Compact (840-2230): How do I verify my installation is working?

Also asked as:

Gateway in secure mode with all nodes commissioned (allow 15 min to reform); node LEDs green/yellow and RS485 LEDs green where devices are expected; all nodes visible in the network map with PDR above 95%; the BACnet MS/TP controller can discover and read devices; save a network map PDF.

Manual section: Setup Guide > Installation Verification; Radio planning > Radiation pattern > Compact (section ID: installation-verification)

See also: Radiation pattern (section ID: radiation-pattern), Wireless best practices (section ID: installation-and-placement-of-wireless-devices-and-external-antennas)

Application

W-BACnet Compact (840-2230): What are the recommended BACnet MS/TP client settings?

Also asked as:

Max 25 BACnet MS/TP devices per wireless network, PDR above 95% on all nodes, APDU timeout 10 s at commissioning (lower it once the network is stable), 3 APDU retries, APDU segment timeout 5 s, max APDU size 480 bytes, Max Master set to the highest MAC address in use on the segment plus a small margin, a higher Max Info Frames on routers and gateways than on field devices, ReadPropertyMultiple (RPM) and/or COV where the device supports it, backup failure timeout 30 s or more, and discovery timeout 10 s or more.

Manual section: Application Guide > Best Practice Settings (section ID: best-practice-settings)

W-BACnet Compact (840-2230): Which baud rates are supported?

Also asked as:

9600, 19200, 38400, 57600, 76800 and 115200. The Compact uses autobaud by default; if autobaud can't find the baud rate, the gateway's settings (Config Distribution) are used. Parity and stop bits aren't configurable in BACnet MS/TP. Use the highest baud rate that every device on the MS/TP segment supports, including routers; this matters most for large transfers such as controller application downloads.

Manual section: Application Guide > MS/TP settings > Baudrate (section ID: baudrate)

W-BACnet Compact (840-2230): How fast should my controller poll?

Also asked as:

No faster than the APDU timeout multiplied by the total number of attempts (1 + number of retries), so that several requests are never outstanding at the same time. Example: a 3 s APDU timeout with 3 retries can take up to 3 × (1 + 3) = 12 s to fail, so poll no faster than every 12 s. Also set polling rates the network can actually support; see the polling configuration guidance.

Manual section: Application Guide > Request frequency (section ID: request-frequency)

W-BACnet Compact (840-2230): What APDU timeout and retries should I use?

Also asked as:

Start at 10 s with 3 retries while the wireless network is commissioned and PDR is verified. The worst-case time to fail is APDU timeout × (1 + number of retries), so 10 s with 3 retries is 40 s. Once the network is stable (PDR 95% or more on all nodes, no recurring timeouts), lower it, but not below the slowest normal response time you observe plus a margin; going from 10 s to 6 s cuts the worst case from 40 s to 24 s per failed request. The timeout and retries are set on the device that sends the request, so when a supervisory controller polls field devices, the controller's own settings apply. Very long timeouts don't make a slow network faster: an offline device blocks every request to it for the full timeout × attempts.

Manual section: Application Guide > APDU timeouts (section ID: apdu-timeouts)

W-BACnet Compact (840-2230): What should I set Max Master and Max Info Frames to?

Also asked as:

Set Max Master to the highest MAC address in use on the MS/TP segment, plus a small margin for future devices, and use the same value on all devices on the segment, including the MS/TP router or gateway. Leaving it at the default of 127 makes every master poll for masters that don't exist, which slows token rotation. Keep MAC addresses as low and contiguous as possible. For Max Info Frames, the default (typically 1) is usually enough on field controllers, but routers and gateways need a higher value because they carry requests from the BACnet client to every device on the segment; a value of 1 makes the router a bottleneck.

Manual section: Application Guide > Max Master (section ID: max-master)

W-BACnet Compact (840-2230): Should I use ReadPropertyMultiple (RPM) or COV?

Also asked as:

Yes, where the device supports them. ReadPropertyMultiple (RPM) bundles many points into one request and cuts the number of transactions over the wireless network dramatically compared to ReadProperty. Check support in the device's Protocol Services Supported property or its PICS, and confirm in the client's debug log or a network capture that the client actually uses RPM, as some clients fall back to single reads. Use COV (Change of Value) for points that change rarely, so the device sends updates only when the value changes.

Manual section: Application Guide > Read Property Multiple (RPM) and COV (section ID: read-property-multiple-rpm-and-cov)

W-BACnet Compact (840-2230): How do I configure polling rates so the network keeps up?

Also asked as:

Check the poll service statistics: if the cycle time for a rate is longer than the configured rate, or utilization stays above about 70–80%, the poller can't keep up. Estimate the cycle time as number of poll requests × average response time; for example, 300 points in about 15 RPM requests at about 1 s each gives about 15 s, so a 30 s rate leaves headroom. Start with conservative rates and shorten them only when the statistics show spare capacity. Use the Fast rate only for points that genuinely need it, put slow-changing values on the Slow rate, poll W-BACnet wireless diagnostic points at the slowest rate or not at all, and remove unused points.

Manual section: Application Guide > Polling configuration (section ID: polling-configuration)

W-BACnet Compact (840-2230): Why are my polling rates never met even though the network is fine?

Also asked as:

Many clients poll a point only while something is subscribed to it, and give the first poll after a subscription priority (dibs polls in Niagara). If points are subscribed and released repeatedly, these priority requests keep pushing ahead of normal polling. Check the share of on-demand or priority polls in the poll statistics; a large share when nobody uses the system, for example at night, means something subscribes automatically, such as scheduled queries or reports, logic reading points indirectly, or supervisors and third-party integrations. Subscribe points that are needed all the time permanently and assign them a polling rate instead.

Manual section: Application Guide > Polling configuration (section ID: polling-configuration)

W-BACnet Compact (840-2230): How should I configure BACnet/IP-to-MS/TP routers?

Also asked as:

Give each MS/TP network a unique BACnet network number and make sure there is only one route to each network. Disable unused MS/TP ports on the supervisory controller, so traffic isn't routed or broadcast twice. Check the router's statistics for errors, retries and token loss, which usually point to wiring, termination, Max Master or MAC address problems.

Manual section: Application Guide > Routing and IP-side configuration (section ID: routing-and-ip-side-configuration)

W-BACnet Compact (840-2230): In what order should I tune a W-BACnet network?

Also asked as:

Verify radio performance first (PDR 95% or more on every node), because parameter tuning does not fix poor signal. Then set baud rate, Max Master and Max Info Frames on all devices and routers; set the client's APDU timeout, segment timeout and retries (start at 10 s / 5 s / 3); confirm RPM is used and enable COV where supported; set polling rates the network can support; move wireless diagnostic points to the slowest rate; remove on-demand subscription churn; and finally reset the poll statistics, observe them for at least a full day, and tighten timeouts and polling rates step by step. Keep the gateway and node firmware up to date.

Manual section: Application Guide > Tuning checklist (section ID: tuning-checklist)

W-BACnet Compact (840-2230): How much latency does the wireless link add?

Also asked as:

About 20 ms per mesh hop on average, up to 50 ms per hop. Total response times of 100 ms to 5 s have been observed depending on network, BACnet MS/TP settings and radio environment. Start with a 10 s response wait time and reduce it as performance allows.

Manual section: Application Guide > Wireless latency / Actual response time / Response wait time (section ID: wireless-latency)

W-BACnet Compact (840-2230): Does W-BACnet support segmentation?

Also asked as:

Yes. W-BACnet supports a max APDU size of 480 bytes, so a 1024-byte response, for example, is split into 3 segments. Each segment must be acknowledged. The recommended APDU segment timeout is 5 s; keep it shorter than the APDU timeout, and lower it once you know how responsive the BACnet servers are.

Manual section: Application Guide > Segmentation / Segment timeouts (section ID: segmentation)

W-BACnet Compact (840-2230): Which BACnet MS/TP features are not supported?

Also asked as:

BACnet MS/TP subordinate (slave) devices (usually MAC 128–254, e.g., some B-ASC, B-SS, B-SA devices; check the device's Protocol Implementation Conformance Statement (PICS) or BTL listing) and BACnet MS/TP extended frames. Only BACnet MS/TP master devices (MAC 0–127) and standard frames are supported.

Manual section: Application Guide > Unsupported features (section ID: unsupported-features)

Remote diagnostics

W-BACnet Compact (840-2230): How do I monitor the wireless performance of my W-BACnet network?

Also asked as:

There are two ways:

Manual section: Mobile App > Network Map > PDR (section ID: pdr); Remote Diagnostics (section ID: remote-diagnostics)

W-BACnet Compact (840-2230): Can I monitor the wireless network from my BMS?

Also asked as:

Yes. The gateway exposes a diagnostics BACnet MS/TP device (default MAC 254, Device ID 165300). Because 254 is a subordinate address it won't answer Who-Is, so add it manually by MAC and Device ID, then read its object list. Objects include uptime, connected devices/nodes, FOTA progress, error counters, and per-node RSSI, PDR, parent, name and link quality (updated every 2 min). On site, connect to the gateway with the W-BACnet mobile app and open the network map: the hexagon next to each node shows its PDR (packet delivery ratio), see Mobile App > Network Map > PDR (section ID: pdr).

Manual section: Remote Diagnostics; BACnet Diagnostic Objects (section ID: remote-diagnostics)

W-BACnet Compact (840-2230): Can I see the wireless diagnostics in Niagara or another BMS?

Also asked as:

Yes. Any BMS that works as a BACnet MS/TP client, such as Niagara, can read them. The gateway exposes a diagnostics device (default MAC 254, Device ID 165300) with objects for uptime, connected nodes, error counters and per-node RSSI, PDR and link quality. MAC 254 doesn't answer Who-Is, so add the device manually in your BMS by MAC address and Device ID, then read its object list. Requires firmware 4.3.0 or later. On site, connect to the gateway with the W-BACnet mobile app and open the network map: the hexagon next to each node shows its PDR (packet delivery ratio), see Mobile App > Network Map > PDR (section ID: pdr).

Manual section: Remote Diagnostics (section ID: remote-diagnostics)

Troubleshooting

W-BACnet Compact (840-2230): The RS485 LED is red / no RS-485 device detected. What do I do?

Also asked as:

Check RS485 polarity and the device's baud rate (the Compact runs autobaud by default; double-press the button to retry). Some devices only pass tokens once another W-BACnet device is on the network, so add one. Confirm the BACnet MS/TP device itself works.

Manual section: Troubleshooting > No RS-485 device detected (section ID: no-rs-485-device-detected)

W-BACnet Compact (840-2230): Nodes aren't connecting to the gateway. What should I check?

Also asked as:

Check which of the two commissioning methods you are using – both are valid, and the mobile app method is preferred. Remember the Compact is always a node, so all mode settings are on the Wall mount or DIN rail gateway. Mobile app method: confirm the gateway's three-pole switch is in the secure-gateway position (Gateway on a DIN rail, ◼ on a Wall mount) and that you tapped Add for the Compact in the app. Physical method: confirm the gateway switch is in the commissioning position (COMM. on a DIN rail, ◻ on a Wall mount) and the Compact is in commissioning mode (blue sweep). In both cases, check that nothing is still in range test mode and that the Compact is within range; move it closer or add repeater nodes.

Manual section: Troubleshooting > Wireless > Nodes are not connecting (section ID: nodes-are-not-connecting-to-gateway)

W-BACnet Compact (840-2230): None of the LEDs light up when powered. What should I check?

Also asked as:

Confirm 12–24 VDC or 24 VAC with at least 0.5 A, and correct DC polarity. Check whether the unit is in bootloader mode using nRF Connect (Scanner, DFU filter); if it appears, follow the update procedure, otherwise power-cycle. If unresolved, contact your distributor.

Manual section: Troubleshooting > None of the LEDs are blinking (section ID: none-of-the-leds-are-blinking-when-powered-on)

W-BACnet Compact (840-2230): Some nodes stay in secure mode after I switched the gateway back to commissioning. Why?

Also asked as:

Those nodes hadn't rejoined the gateway in time to get the instruction. Put the gateway back in secure mode for 10 minutes so all nodes rejoin, then switch to commissioning; or uncommission each node manually (hold button 10 s).

Manual section: Troubleshooting > Wireless (section ID: when-i-put-the-gateway-back-into-commissioning-mode-some-nodes-stay-in-secure-mode)

W-BACnet Compact (840-2230): How long does BACnet MS/TP device discovery take?

Also asked as:

Use a discovery timeout of at least 10 s. Ensure devices are fully booted and token-passing; some only start once another W-BACnet device is on the wireless network.

Manual section: Troubleshooting > BACnet Specific (section ID: how-long-does-it-take-to-discover-the-mstp-device-on-the-trunk)

W-BACnet Compact (840-2230): A node shows red signal or PDR below 94%. How do I fix it?

Also asked as:

Make sure the Compact is not installed inside a metal cabinet or enclosure, check antenna installation and placement, keep antennas clear of metal and obstructions, use an external antenna, reposition the node, or add a repeater to improve the mesh path. Target PDR above 95% on every node.

Manual section: Installation Verification > If a check fails; Radio planning (section ID: if-a-check-fails)

Firmware

W-BACnet Compact (840-2230): What is the latest firmware and how do I check my version?

Also asked as:

Latest is 4.3.1 (released 2026-11-18). Check in the app, or hold the button 15 s and release on cyan: the top LED blinks the major number, the middle LED the minor and the bottom LED the patch (e.g., 3-3-2 blinks = 3.3.2).

Manual section: Firmware Updates > Checking Current Version (section ID: checking-current-version)

W-BACnet Compact (840-2230): How do I update firmware without the W-BACnet app?

Also asked as:

The preferred way to update firmware is always through the W-BACnet app. Use the nRF Connect update flow only if the device runs firmware below 3.0.0, or as a fallback after multiple failed update attempts with the W-BACnet app: download the firmware zip from LumenRadio, install nRF Connect, hold the button for 20 s until the middle LED turns red (bootloader mode), scan and connect to the W-BACnet-DFU device, select the file via the DFU icon and wait for "Application has been sent successfully". Below 3.0.0, FOTA is not available, so every device must be updated this way. From 3.0.0 onwards, update only the gateway and FOTA updates the nodes.

Manual section: Firmware Updates > Update Procedures > nRF Connect (section ID: nrf-connect)

W-BACnet Compact (840-2230): What changed in firmware 4.3.0 and are there known issues?

Also asked as:

Added: better stability/throughput on large networks and wireless diagnostics readable over BACnet MS/TP. Changed: range test auto-exits after 30 min. Fixed: app network-info failures, RS485 intermittent errors, discovery via BACnet/IP-to-MS/TP routers. Known issues: app connection temporarily cuts bandwidth by 33%; downgrading below 3.0.0 factory-resets the device.

Manual section: Firmware Updates > Release Notes > 4.3.0 (section ID: 430)

Support

W-BACnet Compact (840-2230): How long is the warranty and what voids it?

Also asked as:

Warranty length is set by your distributor, typically 1–5 years from shipment. It is void if the product is repaired or modified without LumenRadio approval, or the serial number is missing or illegible. Defects must be reported in writing within 15 days of discovery.

Manual section: Warranty and Support > Warranty Terms / Return and complaint policy (section ID: warranty-terms)

W-BACnet Compact (840-2230): Who should I contact for support and what should I include?

Also asked as:

Contact your installer or distributor first for installation, wiring, power, configuration and warranty questions; contact LumenRadio support for firmware errors (e.g., all LEDs solid red) or unresolved issues via Create Support Ticket. Include symptoms, product/serial/firmware, controller make and model, steps tried, photos, LED video, network map PDF/PDR, power type, bus settings, wireless conditions and antennas used.

Manual section: Warranty and Support > When to Contact Support / What to include (section ID: when-to-contact-support)

W-BACnet Compact (840-2230): How do I file an RMA?

Also asked as:

Submit an RMA claim through the LumenRadio support system with the product serial numbers, a clear fault description, and details of how the device was installed.

Manual section: Warranty and Support > RMA claims (section ID: rma-claims)

Regulatory

W-BACnet Compact (840-2230): What certifications does the product have?

Also asked as:

CE (RED 2014/53/EU), UKCA, FCC Part 15 Class B (FCC IDs XRSTIMOMWAN301, XRSTIMOMWAN201), Industry Canada/ISED, MIC (Japan) and KC (South Korea), with 2.4 GHz approvals listed for China, India, Australia, South Africa, Malaysia and Vietnam. Keep at least 20 cm between antenna and people (FCC exposure).

Manual section: Regulatory Compliance (section ID: regulatory-compliance)

W-BACnet Compact (840-2230): Is the W-BACnet wireless communication encrypted and secure?

Also asked as:

Yes. All data sent over the W-BACnet wireless mesh is encrypted with AES-128, and only devices with the network credentials can join the mesh. Configuration requires physical access to the device, network keys are only shared as encrypted blobs that only W-BACnet devices can decrypt, and firmware updates are signed and verified on every device.

Manual section: Security features (section ID: security-features)

W-BACnet Compact (840-2230): Can W-BACnet be accessed or managed from the internet?

Also asked as:

No. W-BACnet devices have no Ethernet, Wi-Fi or other interface to an external IP network, no border-router function and no cloud or remote management interface. IPv6 is used only for internal addressing inside the encrypted MiraMesh network. The devices cannot be configured, managed or updated from the internet or over the BACnet interface.

Manual section: Interfaces (section ID: interfaces)

W-BACnet Compact (840-2230): Can someone change the W-BACnet configuration over Bluetooth without physical access?

Also asked as:

No. W-BACnet devices do not advertise over Bluetooth Low Energy (BLE) by default. Press the button on the device three times to make it connectable; it then advertises for 3 minutes and stops if no connection is made. A connected session disconnects automatically after 2 minutes of inactivity. The BLE connection uses only the on-chip antenna, so you normally need to be within 2–3 m of the device.

Manual section: Configuration requires physical access (section ID: configuration-requires-physical-access)

W-BACnet Compact (840-2230): How are W-BACnet firmware updates protected?

Also asked as:

Every firmware file is digitally signed. The update is sent from the mobile app over BLE to the gateway, which distributes it to the nodes as AES-128-encrypted mesh messages. The gateway and each node check the signature before installing; if the check fails, that device rejects the update and keeps its current firmware. Updates can only start over BLE, so they need physical access to the gateway.

Manual section: Secure firmware updates (section ID: secure-firmware-updates)

W-BACnet Compact (840-2230): Does W-BACnet comply with the RED cybersecurity requirements (EN 18031)?

Also asked as:

LumenRadio has assessed W-BACnet as outside the scope of RED Article 3(3)(d), because it has no interface to any external IP network and cannot communicate over the internet, so no Notified Body evaluation against EN 18031-1 is required. Article 3(3)(e) does not apply because W-BACnet does not process personal data, and Article 3(3)(f) does not apply because it has no financial functions. W-BACnet still includes security measures in line with the intent of EN 18031-1.

Manual section: EU Radio Equipment Directive – Article 3(3)(d), (e), (f) (section ID: eu-radio-equipment-directive-article-33d-e-f)

W-BACnet Compact (840-2230): What is the system integrator responsible for to keep a W-BACnet installation secure?

Also asked as:

Secure the BMS, BACnet/IP routers and controllers with access control, strong passwords and up-to-date software; install the devices where unauthorized people can't easily reach them, such as locked cabinets or plant rooms; keep the firmware up to date through the mobile app; and treat BACnet MS/TP as unauthenticated by restricting who and what can reach the BACnet network, especially from BACnet/IP.

Manual section: Responsibilities of the system integrator (section ID: responsibilities-of-the-system-integrator)

W-BACnet Compact (840-2230): How do I report a security vulnerability in W-BACnet?

Also asked as:

Submit a request through the LumenRadio support portal. Include the product name, firmware version and a description of the issue, and do not disclose the vulnerability publicly until LumenRadio has had the chance to investigate and respond.