This manual provides technical guidance for integrating the W-BACnet module into your own product. The W-BACnet OEM module is a surface-mounted radio module that adds wireless BACnet MS/TP communication to a host product, replacing the BACnet control cable with a wireless mesh network.
The manual describes the module's features, specifications, pin assignments and mechanical dimensions, guidelines for hardware integration, PCB layout and antenna selection, the SPI and UART management interfaces, commissioning, firmware updates and regulatory compliance.
Product Overview
W-BACnet simplifies BACnet MS/TP installations by replacing the control cable with a wireless connection. This significantly reduces the downsides of running control cables, such as daisy-chaining, installation planning and troubleshooting.
The W-BACnet module is built on LumenRadio's MiraOS, which runs the MiraMesh network stack. MiraMesh is a self-stabilizing mesh network technology that uses patented technology to ensure highly reliable, long-range wireless communication in noisy environments. W-BACnet uses the international license-free ISM band at 2.4 GHz, the same band used by Wi-Fi and Bluetooth. Thanks to Cognitive Coexistence, LumenRadio's patented technology, the modules communicate reliably despite the noise generated by nearby devices.
A W-BACnet network consists of a single W-BACnet Gateway, connected to the BACnet MS/TP controller through its RS485 interface, and up to 100 W-BACnet Nodes, each connected to a BACnet MS/TP device.
Features
Mesh network: cover an entire building by using the mesh network as your infrastructure.
Self-stabilizing: the mesh network continually searches for the best route for packets between each device.
Cognitive Coexistence: LumenRadio's patented technology provides industrial-grade reliability and tolerance to interference.
Agnostic communication: there is no need to have identical baudrate, parity or stop bit configuration on each BACnet device in the same network.
Small footprint: 18.5 mm × 33.5 mm.
Antenna connector: U.FL/I-PEX.
Upgradable firmware: over Bluetooth Low Energy (BLE), see Firmware Update.
Configurable: through the SPI or UART management interface.
Key Specifications
Range: up to 500 m line of sight between two meshing units
Output (ERP): max 20 dBm
Sensitivity: -94 dBm
Link budget: 114 dB
Frequency band: 2.45 GHz ISM band (2402–2480 MHz)
Supply voltage: 3.0–3.6 V
Peak current consumption (typical): 150 mA in high power mode
Operating temperature: -40 °C to +85 °C
See Specifications for the complete electrical and RF specifications.
The W-BACnet module is designed to be simple to use and requires little intervention from an external CPU. This section describes the RS485 interface, how a network of W-BACnet modules is commissioned and decommissioned, how the module detects connected BACnet devices, and what to consider about latency in the wireless mesh network.
The module is configured and monitored through the SPI or UART management interface. Both interfaces have the same capabilities.
RS485 Interface
The RS485 interface of the W-BACnet module consists of 4 digital signals: UART_TXD, UART_RXD, RS485_RE and RS485_DE. Use them to connect an RS485 driver. For the pins, see Pin Assignments, and for an example circuit, see RS485 Reference Design.
{{#warning}}
Signals on the UART_RXD pin must not exceed VDD. For 5 V logic, use a level-shifting circuit, such as a resistor divider.
{{/warning}}
RS485 Bus Configuration
The RS485 configuration can be written to a W-BACnet module regardless of its current app mode.
An RS485 configuration written to a W-BACnet gateway applies to the gateway itself, and also acts as the default for the W-BACnet nodes in the same network. The default can be overridden by writing an RS485 configuration to individual mesh nodes. Mesh nodes other than the one being written are not affected. This allows BACnet devices with different RS485 configurations to communicate in the same BACnet network.
{{#note}}
RS485 configurations written to individual mesh nodes, called local configurations, are lost when the module restarts. The node then uses the default RS485 configuration from the gateway.
{{/note}}
The RS485 configuration is set with RS485_CONFIG in the SPI or UART management interface.
Commissioning
Commission a W-BACnet system in the following steps:
Put the W-BACnet module connected to the BACnet MS/TP controller into Commissioning Gateway mode with APP_MODE in the SPI or UART management interface.
Put the W-BACnet modules connected to the BACnet MS/TP devices into Commissioning Mesh mode with APP_MODE in the SPI or UART management interface.
Modules in Commissioning Mesh mode join the gateway and receive network credentials. To find out when this has happened, read COMMISSIONING in the SPI or UART management interface. When COMMISSIONING is 1, the mesh node is ready. A mesh node usually takes about one minute to join the network, but it can take longer depending on the physical environment, such as walls and radio interference.
Optional: configure the RS485 bus communication parameters with RS485_CONFIG in the SPI or UART management interface. An RS485 configuration written to the gateway is the default for all mesh nodes in the network. Mesh nodes with a locally set RS485 configuration ignore this default. An RS485 configuration written to a mesh node only affects that mesh node. The RS485 configuration can be written both during commissioning and in a secure network.
Optional: when all mesh nodes are ready, as indicated by COMMISSIONING, validate the system by letting the BACnet MS/TP controller poll the BACnet MS/TP devices as if they were connected by a cable.
Set the W-BACnet module connected to the BACnet MS/TP controller to Secure Gateway mode with APP_MODE in the SPI or UART management interface.
When the gateway is set to Secure Gateway mode, it broadcasts a message to all mesh nodes in the network, instructing all modules to perform a synchronized restart after 10 seconds. After the restart, the gateway is in Secure Gateway mode, and all connected nodes are in Secure Mesh mode. The commissioning is now complete. After the synchronized restart, the mesh nodes search for the gateway again, and communicate securely using encryption until they are explicitly decommissioned.
Decommissioning
To decommission a single mesh node from a network, write 1 to DEVICE_RESET in the SPI or UART management interface. The module restarts automatically, and can then be commissioned again.
To decommission an entire mesh network at once, switch the Secure Gateway to any other app mode with APP_MODE in the SPI or UART management interface. The gateway broadcasts a message that instructs the connected nodes to decommission. As described in Commissioning, this broadcast makes the connected mesh nodes perform a synchronized restart 10 seconds after they receive it. After the synchronized restart, each connected mesh node is in Commissioning Mesh mode.
Detection of Connected Devices
A W-BACnet module listens passively on the RS485 bus for activity from connected devices. Once a device has been detected and the module has joined a wireless network, polling starts. A mesh node module supports a single BACnet MS/TP device on the bus, and a gateway module can support several BACnet MS/TP devices for pre-existing networks.
The addresses of the detected devices can be read from SERVER_ADDRESSES in the SPI or UART management interface.
Networking and Latency
W-BACnet is based on MiraMesh. For information on how the networking stack works, see the MiraMesh documentation.
MiraMesh is designed for robustness and power efficiency in radio environments with a lot of interference. This can come at a cost to throughput and latency. While throughput limitations are usually negligible for BACnet, latency requirements can be an issue.
As a general rule, allow 50 ms of round-trip time (RTT) latency per network hop from the root node. For example, a node that is 3 hops away may add 150 ms of latency compared to a cabled solution. Consider this when you configure the timeout parameters of the BACnet MS/TP controller and devices.
We recommend setting the communication timeout parameters of any BACnet MS/TP controller or device to at least 1000 ms.
Specifications
This section lists the electrical and RF specifications of the W-BACnet module.
1 Low-frequency I/O (up to 10 kHz). For detailed information about the pin functionality, see the Nordic Semiconductor nRF52840 product specification.
RF Antenna Connector
To connect an external antenna, use the U.FL connector on the top of the module. The antenna must have a characteristic impedance of 50 ohm at 2.45 GHz. See the Antenna Guideline for more information.
Mechanical Specification
All dimensions are in millimeters.
Module Dimensions
Mechanical design files in .stp and .dxf format are available for download, see Design Files.
Carrier Tape Dimensions
The modules are delivered on reels. The carrier tape has the following dimensions:
Reel Marking
Every reel has an identifier sticker, both on the reel and on the reel package.
The identifier sticker contains the following information:
Hardware Integration
This section describes how to integrate the W-BACnet module into a product.
Integration Overview
The block diagram below shows the components required to integrate the module. The module itself must be soldered onto a carrier board.
To fully integrate the module into a product, the carrier board must provide the following interfaces:
RS485: the connection between the module and other BACnet devices. For an example, see RS485 Reference Design.
SPI or UART management interface: for communication with the W-BACnet module, and to configure its RS485 communication parameters. You can choose either interface; they have the same capabilities.
Push button: press the button while powering up the module to put it into bootloader (DFU) mode. You can also enter this mode with the SPI or UART management interface, without having to power the module off and on.
Antenna: an external antenna is required. See the Antenna Guideline.
Design Files
Electrical and mechanical design files, such as symbols, footprints, drawings and 3D models in .stp and .dxf format, are available for download on the W-BACnet OEM module support page.
Common Integration Mistakes
Integrating the W-BACnet module is a relatively simple process, but for optimal RF performance it is important to follow the Power Supply Recommendations and Layout Considerations. Otherwise, the RF performance may be poor. To avoid the most common mistakes:
The carrier PCB must be of the recommended type and have a proper ground plane.
The product enclosure and the carrier PCB must follow the clearance recommendations.
The product enclosure must not block radio signals.
The power supply pins must have sufficient decoupling.
All ground pins must be connected on the carrier PCB.
The programming pins (P20 and P21) must be accessible.
Power Supply Recommendations
The W-BACnet module is designed for 3.3 V operation. Do not apply a voltage to any of the pins until the 3.3 V rail is connected.
To ensure reliable operation, decouple the supply pin with a 100 nF ceramic capacitor close to the pin. We also recommend adding a high-value ceramic bulk capacitor, such as 47 µF, to reduce the current ripple on the 3.3 V net.
During radio transmission, the current consumption rises sharply to 150 mA typical and 250 mA maximum. The typical slew rate during radio transmission is 300 A/s.
All dimensions are in millimeters unless otherwise specified. Symbols, footprints, drawings and 3D models are available for download, see Design Files.
Module Pad Positions
All positions below are relative to the origin (0, 0) in the image above:
Pin P38: (3.25, 6)
Pin P39: (10, 9.25)
Pin P40: (7.1, 4)
Pin P41: (5.3, 4)
Recommended Footprint
Main pads: oblong 1.4 × 2.79 (the oblong edge is a half circle with a diameter of 1.4)
Small rectangles, left edge: 1.0 × 0.8 (red)
Small squares, right edge: 1.02 × 1.02 (blue)
Large square: 2.0 × 2.0 (green)
Carrier Board Layout Guidelines
The W-BACnet module has been specifically designed to achieve optimal RF performance. To maintain this, follow these guidelines:
Use ground planes on the main board. Good decoupling of any high-speed digital circuitry is a must. Many embedded microprocessors have clock frequencies with clocks or overtones that reach well into the GHz range. An embedded design can pass any EMC certification and still cause disturbances that block the RF reception of the W-BACnet module. The receiver sensitivity of the W-BACnet module is -96 dBm, so we recommend keeping disturbances below -100 dBm in the frequency range of operation.
Make sure that all power paths have low impedance. Connect the power and GND pads to the source with a sufficient amount of copper, using wide traces and proper via coupling.
Use a near-field probe connected to a spectrum analyzer to check for disturbances on the 2.45 GHz band generated by the microprocessor or any other device on the main board. Pay special attention to pre-built LAN products; they pass EMC certifications, but some of them radiate poorly on 2.45 GHz. If you can see disturbances on a spectrum analyzer, the reception of the W-BACnet module will be impaired.
The W-BACnet module has supply voltage decoupling on the circuit board, but the supply voltage must still be properly filtered. If interference or intermittent communication failures occur, check the supply voltage for dropouts, switching ripple and similar problems.
Keep the top layer within the footprint free of copper. There is a ground plane on the W-BACnet module, but there are also supply lines, and relying on the solder mask for isolation is an unnecessary risk.
The purple, diagonally striped area is the routing keep-out area for the top layer. Do not place tracks, vias or other copper shapes in this area.
Antenna Guideline
Antenna selection and design are crucial to achieve good RF performance in your product. Select an antenna with a narrow bandwidth for the 2.4 GHz ISM band (2.4–2.48 GHz) and minimum loss (typically expressed as the S11 parameter or VSWR). Mount the antenna according to the manufacturer's data sheet. Most antennas are not fully omnidirectional, so consider the radiation pattern of the antenna when you position it, so that it is most efficient in the desired directions.
The antenna may be terminated with a connector, usually of the TNC or SMA type. You then need a cable assembly like the one below to connect the antenna to the U.FL/I-PEX connector on the module.
The other option is an antenna fitted with a cable assembly terminated with a U.FL/I-PEX connector that mates with the RF connector on the module.
Antenna Cable Handling
Not only the antenna is important, but also the RF path between the antenna and the module. The RF path must be a transmission line with an impedance of 50 ohm. Handle all cables and connectors that are part of the transmission line with care. Avoid twisting or bending the cable as far as possible.
The U.FL/I-PEX connector on the module needs attention to mate properly. Make sure it snaps into place, but do not use force.
Antenna Placement
As a general rule, allow as much clearance and free space around the antenna as possible. Any object in the path of radiation interferes with the RF performance.
Mount a patch-type (stick-on) antenna on plastic of a well-defined thickness, preferably PC/ABS unless the manufacturer states otherwise. The typical recommended thickness is 1.5–2.0 mm; consult the manufacturer's data sheet. Keep the antenna clear of surrounding objects, especially ground planes and other metal objects. If possible, keep parallel surfaces free from metal objects. For example, if the PCB is right underneath the antenna surface, keep that area free from copper and components. At the very least, keep the minimum clearance distances shown below:
Recommended Antennas
For the European market, make sure that the output power does not exceed 20 dBm, as required by European regulations. The W-BACnet module has been tested against FCC and IC regulatory requirements and is approved with the antennas below, or electrically equivalent antennas.
The LumenRadio 2.15 dBi dipole omnidirectional antenna delivers outstanding performance and orientation flexibility. The antenna can be tilted and swiveled, and has a rugged RP-TNC connector. Combined with the W-BACnet module, the total maximum radiated power is 21.65 dBm (146.2 mW).
Electrical specification
Value
Frequency range
2400–2483.5 MHz
Gain
2.15 dBi
VSWR
< 2
Nominal impedance
50 ohm
Polarization
Vertical
Max power
25 W
Connector
RP-TNC
Length
144 mm
Radome material
TPEE
Radome color
Black
LumenRadio order code
104-1001
Molex 3.2 dBi Balanced Flex Antenna
The Molex 3.2 dBi balanced flex antenna is an adhesive, omnidirectional, flexible antenna. It has a 50 mm cable terminated with a U.FL/I-PEX MHF connector. Combined with the W-BACnet module, the total maximum radiated power is 22.7 dBm (186.2 mW).
Electrical specification
Value
Frequency range
2400–2483.5 MHz
Gain
3.2 dBi
Return loss S11
< -10 dB
Nominal impedance
50 ohm
Polarization
Linear
Connector
U.FL/I-PEX MHF
Length
50 mm
Mounting style
Adhesive
Packaging type
PET film
Radome color
Black
LumenRadio order code
104-1008
Microchip 0.56 dBi Whip Monopole Antenna
The 0.56 dBi whip antenna is a high-efficiency compact antenna with exceptional performance characteristics. Its small size (28.4 mm) makes it ideal for smaller products. Combined with the W-BACnet module, the total maximum radiated power is 20.06 dBm (101.4 mW).
Electrical specification
Value
Frequency range
2400–2500 MHz
Gain
0.56 dBi
VSWR
< 1.3
Nominal impedance
50 ohm
Connector
RP-SMA male
Length
28.4 mm
Radome material
TPEE
Radome color
Black
LumenRadio order code
104-1034
LumenRadio 5 dBi Outdoor Puck Antenna
The LumenRadio 5 dBi omnidirectional puck antenna is well suited for products in a metal enclosure. It has a 1 m RG-174 cable terminated with an RP-SMA male connector. Combined with the W-BACnet module, the total maximum radiated power is 24.5 dBm (281.8 mW).
Electrical specification
Value
Frequency range
2400–2483.5 MHz
Gain
5 dBi
VSWR
< 1.5
Nominal impedance
50 ohm
Polarization
Vertical
Max power
25 W
Connector
RP-SMA male
Cable length
1 m
Size
Ø 45 × 25 mm
Radome material
ABS
Radome color
Black
LumenRadio order code
104-1033
Antennas Without FCC and IC Approval
{{#warning}}
The following antennas have not been tested against FCC and IC regulatory requirements and are not approved for use with the W-BACnet module in the North American market.
{{/warning}}
TE Connectivity 3.2 dBi Dipole Antenna
The TE Connectivity 3.2 dBi dipole antenna is a dome-type panel mount antenna that is available with different types of termination.
Electrical specification
Value
Frequency range
2400–2483.5 MHz
Gain
3.2 dBi
VSWR
< 1.9
Nominal impedance
50 ohm
Max power
5 W
Mounting type
Panel mount
Radome color
Black
LumenRadio order code
104-1027
TE Connectivity 2.1 dBi Monopole Antenna
The TE Connectivity 2.1 dBi monopole antenna is a dome-type panel mount antenna that is available with different types of termination.
Electrical specification
Value
Frequency range
2400–2500 MHz
Gain
2.1 dBi
VSWR
< 2.2
Nominal impedance
50 ohm
Max power
5 W
Mounting type
Panel mount
Radome color
Black
LumenRadio order code
104-1023
Reference Designs
This section provides example designs for the W-BACnet module. Schematic symbols, footprints and 3D models are available for download, see Design Files.
Power Supply Reference Design
The following design can be used as a reference for the power supply circuitry. A buck converter regulates the input voltage to 5 V, which is then converted to 3.3 V by an LDO. The 3.3 V supply (VCC) powers the W-BACnet module, while the 5 V rail can be used to power, for example, the RS485 driver circuit.
RS485 Reference Design
This example shows an RS485 driver implementation. DE, TX, RX and RE are connected to the W-BACnet module as shown in the Module Connection Reference Design.
{{#warning}}
The voltage on RX must not exceed 3.3 V. The RS485 driver (U2) uses 5 V logic levels, and its RO pin (RX) is connected to the module (U1), which has CMOS-level I/Os. A level-shifting circuit, such as the resistor divider in the schematic, must be used.
{{/warning}}
Module Connection Reference Design
This example shows how the W-BACnet module and its peripherals can be connected. See Pin Assignments for a description of the module pins.
Reflow Soldering Specification
The W-BACnet module is a surface-mounted device (SMD) designed for easy integration into high-volume production lines, using reflow soldering onto a PCB. The customer is responsible for selecting a suitable solder paste and for ensuring that the reflow oven temperatures meet the requirements of the solder paste. The W-BACnet module complies with the J-STD-020D1 standard for reflow temperatures.
{{#warning}}
Temperatures must not exceed the minimums or maximums in the table below.
{{/warning}}
Specification
Value
Unit
Temperature inc./dec. rate (max)
3
°C / sec
Temperature decrease rate (goal)
2–3
°C / sec
Soak temp increase rate (goal)
0.5–1.0
°C / sec
Flux soak period (min)
70
sec
Flux soak period (max)
120
sec
Flux soak temp (min)
150
°C
Flux soak temp (max)
190
°C
Time above liquidus (max)
70
sec
Time above liquidus (min)
50
sec
Time in target reflow range (goal)
30
sec
Time at absolute peak (max)
5
sec
Liquidus temperature (SAC305)
218
°C
Lower target reflow temperature
225
°C
Upper target reflow temperature
250
°C
Absolute peak temperature
260
°C
Verification and Testing
Design Verification
LumenRadio operates a full RF laboratory in Sweden and can offer design verification and testing services. Contact LumenRadio for advice.
Production Testing
All W-BACnet modules go through numerous production tests and quality checks before they are shipped. However, we advise you to include some level of testing in the overall test process of your product. LumenRadio is happy to advise on production testing; contact LumenRadio for advice.
Management Interfaces
The W-BACnet module is configured and monitored by the host product through one of two management interfaces:
The SPI Interface, a register-based interface with an interrupt signal.
The UART Interface, a text-based interface that uses ASCII commands.
Both interfaces have the same capabilities, so choose the one that suits your product best. Through either interface, the host product can, for example, set the app mode to commission the network, configure the RS485 bus parameters, read the network status and the detected BACnet devices, enable Bluetooth for the W-BACnet app, and put the module into bootloader mode for a firmware update.
Both interfaces are initialized 1500 ms after the W-BACnet module has started booting. Communicating with the module before that can give unexpected results.
SPI Interface
The Serial Peripheral Interface (SPI) allows communication with and configuration of the W-BACnet module.
The SPI is initialized 1500 ms after the W-BACnet module has started booting. Communicating with the module through the SPI before that can give unexpected results.
A reset of the SPI master, or interruptions on the chip select line, may cause the module to become unresponsive. The module recovers after 5 seconds, and any SPI transactions attempted during this time time out.
SPI Signals
The interface consists of five digital signals (VDD max):
IRQ: interrupt request, active low, configurable with the IRQ_MASK register
The data on the SPI bus is clocked with the most significant bit first. All multi-byte register data is sent in big-endian byte order.
Clock Polarity
Data is valid on the low-to-high transition of SCK. In other words, the clock is active high, with valid data on the leading clock edge.
Maximum Clock Speed
The maximum clock speed supported by the W-BACnet module is 4 MHz. Clock speeds above this limit may result in unexpected behavior.
Setup Time
The SPI slave has a setup time of 4 μs after the high-to-low transition of the CS signal.
SPI Transactions
All SPI transactions start with a high-to-low transition on the CS pin. The CS pin must be held low during the entire SPI transaction.
The IRQ_FLAGS register is always shifted out as the first byte of each transaction.
SPI Commands
All SPI command sequences, except for the NOP command, consist of two SPI transactions. The first transaction uses two bytes, which make up the command. The second transaction carries the payload, and must not be started until the W-BACnet module has acknowledged the command with a high-to-low transition on the IRQ pin. The first byte sent in the second transaction is ignored; we recommend sending 0xFF. The example below shows a full SPI command sequence.
The available SPI commands are listed in the table below. XX is any valid 1-byte register address, and -- are values that are ignored.
Command
Hex value
Description
READ_REG
0x00XX
Read from a register.
WRITE_REG
0x01XX
Write to a register.
NOP
0xFF--
No operation. Can be used as a shortcut to read the IRQ_FLAGS register. The last byte is not used.
SPI Interrupts
The IRQ pin indicates two things:
There are pending interrupts that were enabled through the IRQ_MASK register.
The SPI slave is ready for the second transaction of an ongoing SPI command sequence.
The IRQ pin always goes high (inactive) after a successful SPI command sequence.
The pin goes from high to low when interrupts are pending, or when the module is ready for the second transaction of an SPI command sequence.
SPI Register Map
The table below lists all registers available through the SPI. The first column is the single-byte address of each register. The second column contains the register and field names; the fields of a register are listed below it. The "Bit" column is the bit positions that the field occupies in the register. The "Type" column shows whether the field is read-only (R), write-only (W) or read-write (R/W).
The "Reset value" column is the default value of each field, in hexadecimal format: the value when the module is factory new, or after DEVICE_RESET has been set to 1. A reset value of - means either that the field is write-only, or that its value depends on circumstances. For example, the reset value of ANTENNA_SELECTOR depends on whether the module is an MWA-N2 or an MWA-N3 module, since only the MWA-N3 has an internal antenna.
This register contains information about the network status of the module.
NETWORK_STATUS (SPI)
This field is read-only and shows roughly how stable the connection to the network is.
To perform network operations successfully, such as changing the network baudrate or app mode, we recommend doing them when the value of NETWORK_STATUS is 1 or 2.
Modules in a gateway mode always have the value 1 in this field, since the link quality is measured relative to the gateway.
Value
Meaning
0
Not connected to a network
1
Connected, good link
2
Connected, ok link
3
Connected, unreliable link
COMMISSIONING (SPI)
This field is read-write, and shows whether the module has received network commissioning data.
Setting this bit to 1 factory resets the module, which has exactly the same effect as setting DEVICE_RESET to 1. This reverts the COMMISSIONING field to 0. See DEVICE_RESET for more information about this behavior.
The table below shows the meaning of each value when read, and the number of restarts when the value is written:
Value
Meaning (when read)
Restarts (when written)
0
No commissioning data received yet
0
1
Valid commissioning data received
2
MODE Register (SPI)
This register contains information about the current state of the application.
APP_MODE (SPI)
This field is read-write and sets the app mode of the module. A factory-new module boots into mode 0 (None). The application detects this and switches to the default mode 4 (Commissioning Mesh Mode), which causes a restart. In other words, a factory-new module restarts once after booting. Writing 1 to DEVICE_RESET factory resets the module manually. Writing 0 or 4 to APP_MODE puts the module in Commissioning Mesh Mode.
Idle Mode prevents the module from performing any networking, and puts it in a kind of sleep. No configuration is erased when switching to this mode, so the module can be put back into a secure mode and connect to a previously saved network.
Set when the NETWORK_STATUS field has changed. Only valid for modules in Commissioning Mesh Mode (4) or Secure Mesh Mode (3), see APP_MODE.
The flag is cleared when the STATUS register, which includes the NETWORK_STATUS field, is read.
PING Interrupt Flag (SPI)
Set when the PING_STATUS field is set to 1. The flag is cleared when the PING register is read.
Clear the flag as soon as possible to avoid missing subsequent pings.
TRANSACTION_ERROR Interrupt Flag (SPI)
Always check this bit. A 1 in this bit means that the module cannot process the current transaction, and the full command sequence must be sent again.
VERSION Register (SPI)
This register is read-only, and contains the firmware version that the module runs.
FIRMWARE_VERSION (SPI)
This field contains three bytes: the major, minor and patch version of the firmware on the module. See Firmware Update for how to get and install the latest firmware.
RS485_CONFIG (SPI)
This register is read-write, and is used to read and configure the RS485 bus baudrate.
BAUDRATE (SPI)
The standard baudrates 9600 bps, 19200 bps, 38400 bps and 76800 bps have been tested and verified. Higher values, such as 115200 bps, are allowed but have not been tested. The default baudrate is 0 bps.
RESET Register (SPI)
This register is used to wipe configurations on the module.
DEVICE_RESET (SPI)
This field is write-only, and factory resets the module manually. A factory reset restores the module to the state it was in at its first boot by wiping all modified configurations. It wipes the network credentials and RS485 configurations, and reverts all registers and fields to their reset values (see SPI Register Map).
A device reset causes 2 restarts of the module. The first one happens after the configuration is wiped, which also sets APP_MODE to 0. After the first restart, the application detects that APP_MODE is 0 and switches to the default app mode, 4. This switch causes the second restart, after which the module is in Commissioning Mesh Mode. See APP_MODE for more about this behavior.
Value
Meaning (when written)
Restarts (when written)
1
Perform a factory reset
2
NETWORK_RESET (SPI)
This field is write-only. When set to 1, it wipes any saved network credentials. Other configurations, such as the RS485 bus parameters, are not affected.
In practice, this means that modules in Secure Mesh Mode or Commissioning Mesh Mode leave any network they have joined. For modules in a gateway mode, a network reset clears previously saved network credentials. Such credentials exist if the module was previously in a mesh mode and connected to a network, and was later switched to a gateway.
Value
Meaning (when written)
Restarts (when written)
1
Wipe network credentials
1 if in Secure Mesh Mode, 0 otherwise
BACNET_STATUS Register (SPI)
This register is used to read BACnet-related data from the module.
SERVER_ADDRESSES (SPI)
This field contains the single-byte address of each set or detected BACnet device. A byte equal to 0xFF is an empty slot, with no address.
Value
Meaning
0xFF
No BACnet MS/TP device set or detected
Anything else
Address of a set or detected BACnet MS/TP device
GENERAL_REQUESTS Register (SPI)
This register contains fields that perform various application-related actions.
ANTENNA_SELECTOR (SPI)
This field selects either the internal or the external antenna for wireless communication. Switching antenna is always followed by a restart.
{{#note}}
MWA-N2 modules do not have an internal antenna, so never change this field on them.
{{/note}}
Value
Meaning
Restarts (when switched to)
1
Internal antenna selected
1
2
External antenna selected
1
BLUETOOTH_ENABLED (SPI)
This field is read-write, and controls Bluetooth Low Energy (BLE) advertising for connections from the W-BACnet app. The module advertises for 3 minutes after Bluetooth is enabled. The W-BACnet app can be downloaded from the App Store and Google Play.
When the app is connected to a Secure Gateway with firmware version 3.1.0 or later, the app can update the firmware and show the network map. It also shows the installed firmware version.
The network map shows how many devices are in the network, and how their packets are routed through the mesh network. It also shows which BACnet addresses are connected to which W-BACnet module, and lets you name the W-BACnet modules.
The app can also connect to a mesh node, but then it only shows the firmware version.
Value
Meaning (when written)
0
BLE advertising disabled
1
BLE advertising enabled
PROTOCOL_SELECTOR (SPI)
Reads or changes the active communication protocol.
Value
Meaning
1
Modbus protocol is active
2
BACnet protocol is active
DEVICE_NAME Register (SPI)
This register is read-write, and is used to get or set the device name. The device name identifies the module in the W-BACnet app.
ASCII_CHARACTERS (SPI)
Each byte contains one printable ASCII character, up to a maximum of 20 bytes.
PING Register (SPI)
This register handles the device ping function.
Ping is a command that can be sent from the W-BACnet app to help locate a device. On the boxed W-BACnet products, for example, the LEDs flash.
When the OEM module is pinged, it sets the PING_STATUS field to 1. If the ping interrupt is enabled, an interrupt is raised when the module is pinged.
The ping status and the ping interrupt flag are cleared when the PING_STATUS field is read.
PING_STATUS (SPI)
This field is read-only, and contains the ping status of the module. When the module is pinged from the mobile app, the field is set to 1. Reading this field clears the status and the ping interrupt flag, if enabled.
DIAGNOSTICS Register (SPI)
This register configures diagnostics.
DIAGNOSTICS_ADDRESS (SPI)
This field is read-write and holds the single-byte address used for diagnostics requests. Any value between 128 and 254, or 0 to disable, is accepted. The value is kept across restarts, and reverts to 0 after a DEVICE_RESET.
If set to 0, the module does not respond to diagnostics requests.
DIAGNOSTICS_DEVICE_ID (SPI)
This field is read-write, and is used to read and configure the BACnet device ID of the W-BACnet module. The device ID is used in BACnet diagnostics requests and responses, and can be set to any value between 0 and 4194302. The value is kept across restarts. The default value is 0. Diagnostics are enabled or disabled with DIAGNOSTICS_ADDRESS, not with the device ID.
SPI Usage Example
SPI Example Implementation
A reference implementation is available on LumenRadio's GitHub. It shows how to communicate with the module over SPI, and includes a set of tests to help verify your connection and the module's functionality.
The program is built on the Zephyr RTOS, which supports a wide range of boards. If your target board is not already supported, add a devicetree overlay file (.overlay) in the boards/ directory.
SPI Pseudocode Example
Below is a simple pseudocode example that reads the RS485 configuration through the SPI. The SPI is assumed to be initialized before this code runs.
/* Buffers must be large enough to hold the register and commands */
uint8_t rx_buffer[BUF_SZ];
uint8_t tx_command[2];
tx_command[0] = 0x00; // Read command
tx_command[1] = 0x06; // Address of RS485_CONFIG
/* Transfer the command bytes, read back the IRQ flags in the first byte */
spi_transfer(tx_command, 2, rx_buffer, 1);
/* Wait until the transfer completes */
WAIT_UNTIL(spi_transfer_complete());
/* Wait for the IRQ indicating that the response is ready */
WAIT_UNTIL(gpio_value(SPI_IRQ) == 0);
/* Read the value. The baudrate is 3 bytes long, plus one for the IRQ flags */
spi_transfer(tx_command, 2, rx_buffer, 3 + 1);
/* Wait until the transfer completes */
WAIT_UNTIL(spi_transfer_complete());
/* The IRQ flags are stored in rx_buffer[0] */
/* The baudrate is multi-byte, MSB first */
uint32_t baudrate = (rx_buffer[1] << 16) |
(rx_buffer[2] << 8) |
(rx_buffer[3] << 0);
UART Interface
{{#note}}
The UART management interface is available from firmware version 3.2.0. To update modules with older firmware, see Firmware Update.
{{/note}}
The UART management interface allows communication with and configuration of the W-BACnet module.
The UART interface is initialized 1500 ms after the W-BACnet module has started booting. Communicating with the module through the UART interface before that can give unexpected results.
The interface uses two digital signals (VDD max):
TX: transmitter signal
RX: receiver signal
Connect the RX of the UART cable to the UART_MGMT_TX pin, and the TX of the cable to the UART_MGMT_RX pin. See Pin Assignments for the pins.
UART Configuration
The UART management interface uses the following communication parameters:
Baudrate
Parity
Stop bits
115200
None
1
UART Timing Requirements
Each UART frame must be separated by 100 ms of silence on the bus. Less than 100 ms between the end of one frame and the start of the next gives unexpected results.
UART Commands
UART commands and responses consist of ASCII characters. Send each command separately, following the timing requirements. There are two kinds of commands: read commands and write commands.
A UART command starts with the character r or w, for a read or a write command. The first character is followed by the separator : and a register name (see UART Registers). In write commands, the separator is used again to add write parameters. The command ends with a carriage return followed by a new line: \r\n.
The syntax also has the following properties:
Numeric values are always read and written in decimal form.
All text is case-insensitive, so commands can also start with R or W, and a register name can be written as, for example, REG_NAME, reg_name or rEg_NaMe. For consistency, this manual writes the command in lowercase and the register name in uppercase.
Read Commands
Read commands have the following format, where REG_NAME is any readable register (see UART Registers):
r:REG_NAME\r\n
When a read command is successful, the response has the format below, where REG_NAME is the register and VALUE is the value read from the register:
ok:REG_NAME:VALUE\r\n
A register can also have no value, as with SERVER_ADDRESSES when no BACnet devices are detected:
ok:REG_NAME:\r\n
Write Commands
Write commands have the following format, where REG_NAME is any writable register (see UART Registers) and PARAM is any valid write parameter:
w:REG_NAME:PARAM\r\n
Some registers take more than one parameter:
w:REG_NAME:PARAM1:PARAM2\r\n
When a write command is successful, the response repeats the request exactly, but starts with ok instead of w. See the UART syntax examples.
Responses and Errors
Responses have almost the same format as reads and writes, but start with ok: when the command was successful, and with error: otherwise. An error message is returned when the command is invalid. For example, if the command does not end with \r\n, the response is an error.
UART Syntax Examples
/* Read examples */
/* The response 4 shows that the module is in Commissioning Mesh Mode */
>> r:APP_MODE\r\n
>> ok:APP_MODE:4\r\n
/* The value after the register name is baudrate = 9600 */
>> r:RS485_CONFIG\r\n
>> ok:RS485_CONFIG:9600\r\n
/* There is no register named 'APP' */
>> r:APP\r\n
>> error:UNKNOWN_REGISTER\r\n
/* The command must end with both carriage return '\r'
and new line '\n' */
>> r:APP_MODE\n
>> error:INCORRECT_TERMINATION\r\n
/* Write examples */
/* The register is written successfully with the value 2 */
>> w:APP_MODE:2\r\n
>> ok:APP_MODE:2\r\n
/* The register is written with baudrate = 38400 */
>> w:RS485_CONFIG:38400\r\n
>> ok:RS485_CONFIG:38400\r\n
/* There is no register named 'APP' */
>> w:APP\r\n
>> error:UNKNOWN_REGISTER\r\n
UART Registers
The table below lists all registers available in the UART management interface. The "Type" column shows whether the register is read-only (R), write-only (W) or read-write (R/W).
The "Reset value" column is the default value of the register: the value when the module is factory new, or immediately after DEVICE_RESET has been set to 1. A reset value of - means either that the register is write-only, or that its value depends on circumstances. For example, the reset value of ANTENNA_SELECTOR depends on whether the module is an MWA-N2 or an MWA-N3 module, since only the MWA-N3 has an internal antenna.
This register is read-only and contains the network status of the module. It holds two values: the first shows whether the module has received network commissioning data, and the second shows roughly how stable the connection to the network is. To perform network operations reliably, such as changing the network baudrate or app mode, we recommend doing them when the value of NETWORK_STATUS is 1:1 or 1:2.
{{#note}}
Modules in a gateway mode always have the value 1 in the LINK_QUALITY value, since the link quality is measured relative to the gateway.
{{/note}}
/* The response when reading NETWORK_STATUS has this format: */
>> ok:NETWORK_STATUS:<COMMISSIONING>:<LINK_QUALITY>\r\n
/* An example with real values: */
>> r:NETWORK_STATUS\r\n
>> ok:NETWORK_STATUS:1:1\r\n
COMMISSIONING shows whether network credentials have been received, that is, whether the module has joined a network.
Value
Meaning
0
No commissioning data received yet
1
Valid commissioning data has been received
LINK_QUALITY shows how stable the current network connection is.
Value
Meaning
0
Not connected to a network
1
Connected, good link
2
Connected, ok link
3
Connected, unreliable link
APP_MODE (UART)
This register is read-write and sets the app mode of the module. A factory-new module boots into mode 0 (None). The application detects this and switches to the default mode 4 (Commissioning Mesh Mode), which causes a restart. In other words, a factory-new module restarts once after booting. Writing 1 to DEVICE_RESET factory resets the module manually. Writing 0 or 4 to APP_MODE puts the module in Commissioning Mesh Mode.
Idle Mode prevents the module from performing any networking, and puts it in a kind of sleep. No configuration is erased when switching to this mode, so the module can be put back into a secure mode and connect to a previously saved network.
The table below lists all app modes, and the number of restarts when switching to each mode:
Value
Meaning
Restarts (when written)
0
None (reverts to default)
2
1
Secure Gateway Mode
1
2
Commissioning Gateway Mode
1
3
Secure Mesh Mode
1
4
Commissioning Mesh Mode (default)
1
5
Idle Mode
1
FIRMWARE_VERSION (UART)
This register is read-only and contains the firmware version that the module runs. The module responds with the major, minor and patch version in the following format:
This register is write-only and puts the module into bootloader (DFU) mode, so that the firmware can be updated.
Value
Meaning
Restarts (when written)
1
Enter bootloader (DFU) mode
1
RS485_CONFIG (UART)
This register is read-write, and is used to read and configure the RS485 baudrate.
/* Read example */
>> r:RS485_CONFIG\r\n
>> ok:RS485_CONFIG:9600\r\n
/* Write example */
>> w:RS485_CONFIG:9600\r\n
>> ok:RS485_CONFIG:9600\r\n
Baudrate: the standard baudrates 9600 bps, 19200 bps, 38400 bps, 57600 bps, 76800 bps and 115200 bps have been tested and verified. The default baudrate is 0 bps, which means that the module receives its RS485 configuration from the gateway once it has connected. We recommend setting RS485_CONFIG with the correct baudrate each time the module is powered on.
DEVICE_RESET (UART)
This register is write-only and factory resets the module. A factory reset restores the module to the state it was in at its first boot. Among other things, it wipes the network credentials and RS485 configurations, and resets all register values.
A device reset causes 2 restarts of the module. The first one happens after the configuration is wiped, which also sets APP_MODE to 0. After the first restart, the application detects that APP_MODE is 0 and switches to the default app mode, 4. This switch causes the second restart, after which the module is in Commissioning Mesh Mode. See APP_MODE for more about this behavior.
Value
Meaning
Restarts (when written)
1
Perform a factory reset
2
NETWORK_RESET (UART)
This register is write-only. When set to 1, it wipes any saved network credentials. Other configurations, such as the RS485 bus parameters, are not affected.
In practice, this means that modules in Secure Mesh Mode or Commissioning Mesh Mode leave any network they have joined. For modules in a gateway mode, a network reset clears previously saved network credentials. Such credentials exist if the module was previously in a mesh mode and connected to a network, and was later switched to a gateway.
Value
Meaning
Restarts
1
Wipe network credentials
1 if in Secure Mesh Mode, 0 otherwise
SERVER_ADDRESSES (UART)
This register is read-only, and contains the address of each detected BACnet device as a list of decimal numbers separated by :.
If no devices are detected, reading the register gives no values:
This register is read-write, and selects either the internal or the external antenna for wireless communication. Switching antenna always causes one restart.
{{#note}}
MWA-N2 modules do not have an internal antenna, so never change this register on them.
{{/note}}
Value
Meaning
Restarts (when changed)
1
Internal antenna selected
1
2
External antenna selected
1
BLUETOOTH_ENABLED (UART)
This register is read-write, and enables Bluetooth Low Energy (BLE) advertising for connections from the W-BACnet app. The module advertises for 3 minutes after Bluetooth is enabled, and then stops. The W-BACnet app can be downloaded from the App Store and Google Play.
When the app is connected to a module in Secure Gateway mode with firmware version 3.1.0 or later, the app can update the firmware and show the network map. It also shows the installed firmware version.
The network map shows how many devices are in the network, and how their packets are routed through the mesh network. It also shows which BACnet addresses have been detected by which W-BACnet module, and lets you name the W-BACnet modules.
The app can also connect to a module that is not a gateway, but then it only shows the firmware version and the number of connected BACnet devices.
Value
Meaning
0
BLE advertising disabled
1
BLE advertising enabled
DEVICE_NAME (UART)
This register is read-write, and is used to get or set the device name. The device name identifies the module in the W-BACnet app. The maximum device name length is 20 bytes, where each byte contains one printable ASCII character.
PROTOCOL_SELECTOR (UART)
Reads or changes the active communication protocol.
Value
Meaning
1
Modbus protocol is active
2
BACnet protocol is active
PING (UART)
This register is read-only and handles the device ping function.
Ping is a command that can be sent from the W-BACnet app to help locate a device. On the boxed W-BACnet products, for example, the LEDs flash.
When the OEM module is pinged, it sets the PING register to 1. The ping status is cleared when the PING register is read.
DIAGNOSTICS_ADDRESS (UART)
This register is read-write and holds the single-byte address used for diagnostics requests. Any decimal value between 128 and 254, or 0 to disable, is accepted. The value is kept across restarts, and reverts to 0 after a DEVICE_RESET.
If set to 0, the module does not respond to diagnostics requests.
DIAGNOSTICS_DEVICE_ID (UART)
This register is read-write, and is used to read and configure the BACnet device ID of the W-BACnet module. The device ID is used in BACnet diagnostics requests and responses, and can be set to any value between 0 and 4194302. The value is kept across restarts. The default value is 0. Diagnostics are enabled or disabled with DIAGNOSTICS_ADDRESS, not with the device ID.
UART Usage Example
A simple way to get started is a USB-to-serial interface cable, such as the FTDI USB-RS232-WE-1800-BT_0.0. Wire the cable to the W-BACnet module (see Pin Assignments) and connect it to a computer. Open a serial terminal with the correct parameters, and start communicating with the module.
Below is a simple pseudocode example that reads the app mode. The UART is assumed to be initialized and configured correctly before this code runs.
/* The buffers must be large enough to hold the responses */
uint8_t rx_buffer[BUF_SZ];
uint8_t tx_command[BUF_SZ];
/* Prepare the command that reads the app mode */
size_t tx_len = strlen("r:APP_MODE\r\n");
memcpy(tx_command, "r:APP_MODE\r\n", tx_len);
/* Send the command bytes over UART */
uart_tx(tx_command, tx_len);
/* Receive the response over UART */
size_t rx_len = uart_rx(rx_buffer, BUF_SZ);
/* In Commissioning Mesh Mode, the response is "ok:APP_MODE:4\r\n" */
/* Check the first and last two bytes to confirm that a complete response was received */
if (rx_buffer[0] == 'o' && rx_buffer[1] == 'k' &&
rx_buffer[rx_len - 2] == '\r' && rx_buffer[rx_len - 1] == '\n')
{
int app_mode = rx_buffer[rx_len - 3] - '0'; // Extract the APP_MODE value
}
Development Kit
The W-BACnet Development Kit simplifies evaluation and prototyping with the W-BACnet module. The kit contains the parts needed to build a prototype and integrate the module into your product:
2 × W-BACnet devices
1 × W-BACnet development board
1 × W-BACnet shield
5 × W-BACnet OEM modules
1 × patch antenna
1 × dipole antenna
1 × outdoor dome antenna
1 × micro USB cable
The W-BACnet development board has a W-BACnet module mounted, and is powered through USB or the pin headers. A development shield with an RS485 interface is included and can be attached to the pin headers. The shield also has headers for the SPI and UART management pins. The figure below shows the development board with the shield attached.
Development Kit Demonstration Video
The video "One-Hour Engineering Prototype Challenge" shows how a prototype can be built from scratch with the W-BACnet development kit.
Powering the Development Board
Power the development board with the included USB cable, connected to the J6 micro USB port labeled "USB IMCU". If the board does not power on, check that this port is selected with the power supply selector (S1).
The jumpers and switches are set at the factory and should not be changed. If the board malfunctions, remove the shield from the main board and check the jumpers and the DIP switch positions.
Switch S1 must be set to "USB IMCU", and the J1, J9 and J10 header pins must be connected with jumpers, as shown in the picture below. On J1, VDD and VDD MIRA must be connected. J9 and J10 are reserved.
Development Shield
The shield has additional components to simplify getting started with the W-BACnet module, such as an RS485 interface (J3), SPI (J4) and UART management (J5). It also has a bootloader entry button, and LEDs that indicate power OK and traffic on the communication buses. The shield is powered by the development board.
Configure the module through the SPI or UART management interface.
The relevant pins of the shield are listed below. The UART_TXD and UART_RXD pins are listed so that the RS485 IC can be bypassed.
Pin
Name
Pin type
Description
J4.1
CS
Digital output
SPI chip select, active low
J4.3
MISO
Digital output
SPI Master In, Slave Out
J4.5
MOSI
Digital input
SPI Master Out, Slave In
J4.7
SCK
Digital input
SPI clock
J4.9
IRQ
Digital output
SPI interrupt signal, active low
J5.1
UART_MGMT_TXD
Digital output
UART management TXD
J5.3
UART_MGMT_RXD
Digital input
UART management RXD (3.3 V max)
J5.5
GND
Power
Signal ground
J5.7
3V3
Power
3.3 V supply output
J5.9
BOOTLOADER / push button
Digital input
Bootloader entry (3.3 V max, pulled up)
JP12.2
UART_TXD
Digital output
UART TXD
JP1.4
UART_RXD
Digital input
UART RXD (3.3 V max)
JP1.3
RS485_DE
Digital output
RS485 driver enable
JP1.3
RS485_RE
Digital output
RS485 receiver enable (active low)
Legacy Development Shield
Development kits shipped before 2025 have an earlier version of the shield, without some improvements such as indicator LEDs and a push button. The basic functions, such as RS485, SPI and UART management, are the same.
The LEDs, the three-position switch and the DIP switch on the legacy shield are not used by the W-BACnet module. Configure the module through the SPI or UART management interface.
The relevant pins of the legacy shield are listed below. The UART_TXD and UART_RXD pins are listed so that the RS485 IC can be bypassed.
Pin
Name
Pin type
Description
J4.1
CS
Digital output
SPI chip select, active low
J4.3
MISO
Digital output
SPI Master In, Slave Out
J4.5
MOSI
Digital input
SPI Master Out, Slave In
J4.7
SCK
Digital input
SPI clock
J4.9
IRQ
Digital output
SPI interrupt signal, active low
JP12.2
UART_TXD
Digital output
UART TXD
JP1.4
UART_RXD
Digital input
UART RXD (3.3 V max)
JP12.5
UART_MGMT_TXD
Digital output
UART management TXD
JP12.8
UART_MGMT_RXD
Digital input
UART management RXD (3.3 V max)
JP10.3
BOOTLOADER / push button
Digital input
Bootloader entry (3.3 V max, pulled up)
Development Kit Antennas
The development kit includes 3 antennas of different size, form factor and performance for evaluation. For antennas approved for use in your product, see Recommended Antennas.
Compact Patch Antenna
The compact patch antenna is a flat, adhesive-mount patch antenna for ABS or PC plastic enclosures. It is an ultra-compact indoor antenna with an adhesive back for easy "peel and stick" mounting, designed to be mounted on the inside of an ABS/PC plastic enclosure with a thickness of 2 mm. Its performance is moderate compared to the other antennas, and the range is typically limited to 500 meters line of sight with the W-BACnet module.
Manufacturer product number
Digi-Key order code
YF0027AA
WM12218-ND
1461530100 (alternative)
WM12218-ND
Dome Antenna for Outdoor Use
The dome antenna from Linx Technologies is suitable for relatively compact mounting in outdoor environments. Mount it on a grounded metal surface for optimal performance. With this antenna, the W-BACnet module reaches its full range of up to 1500 meters line of sight.
Manufacturer product number
Digi-Key order code
ANT-DB1-WRT-MON-UFL
ANT-DB1-WRT-MON-UFL-ND
2.15 dBi Omni Antenna
The omnidirectional antenna from LumenRadio gives the best performance of the antennas in the development kit. It has an RP-TNC male connector, so it requires an I-PEX adapter cable. With this antenna, the W-BACnet module reaches its full range of up to 1500 meters line of sight.
The W-BACnet OEM module runs the same firmware as the other W-BACnet products. The latest firmware version is 4.3.1. The changes in each version are listed in the Release Notes.
The firmware version of a module can be read from FIRMWARE_VERSION in the SPI or UART management interface.
Firmware Update via the W-BACnet App
This method is available for modules with firmware version 3.1.0 or later.
The W-BACnet app is available for iOS and Android. When you start the app, it shows a scanning screen with the instruction "Set your device to app mode".
To connect the app to the module, enable Bluetooth on the module: set BLUETOOTH_ENABLED to 1 in the SPI or UART management interface. The app can then connect to the module for 3 minutes.
If a firmware update is available for the connected module, the app shows an option to start the update, and shows the progress in real time.
If you update a gateway, the update automatically propagates to all nodes in the network. This typically takes 30 minutes to 2 hours, but can take longer depending on the size of the network.
Switching Update Channel
To update to beta firmware, switch the update channel: while the app is starting, tap the LumenRadio logo 8 times and select Beta mode.
Firmware Update via nRF Connect
The firmware of the W-BACnet module can also be updated with Nordic Semiconductor's nRF Connect app, available for mobile and desktop.
To update the module, first put it in bootloader (DFU) mode in one of two ways:
Set BOOTLOADER_ENABLED to 1 in the SPI or UART management interface.
Drive the BOOTLOADER pin low while you reset the module with the nRESET pin (see Pin Assignments). Once the module has booted into DFU mode, the BOOTLOADER pin no longer needs to be driven.
In DFU mode, the module appears in the list of Bluetooth devices in nRF Connect. Connect to the module, and update it with the firmware zip file from the W-BACnet support page, which also has detailed instructions.
The module boots into application mode again if there has been no BLE activity for 2 minutes. A reset with the nRESET pin also boots the module into application mode immediately.
Known Compatibility Issues
Downgrading from firmware 3.2.x to 2.2.3 uncommissions the module.
Downgrading from firmware 3.2.x to 2.1.1 makes the module non-functional. It can still be upgraded again with the nRF Connect mobile app, see Firmware Update via nRF Connect.
Downgrading a DIN rail PRO device from firmware 3.2.x to 3.0.0 bricks the device.
Release Notes
4.3.1
Released on 2026-11-18.
Added
W-BACnet now provides diagnostics objects for autobaud status and RS-485 backoff events on each node.
W-BACnet Gateways can now disable autobaud for all Compact devices in the network using the push button.
Changed
More robust wireless metadata handling.
Fixed
Improved RS-485 handling for installations with multiple devices on the bus.
W-Modbus: Fixed solar-mode write timeouts and improved write, broadcast and response handling.
Known Issues
While the W-BACnet/W-Modbus mobile app is connected to a W-BACnet/W-Modbus device, the device bandwidth is temporarily reduced by 33%.
Downgrading the firmware to a version below 3.0.0 will factory reset the device.
4.3.0
Released on 2026-09-07.
Added
W-BACnet: Improved network stability and throughput on large networks.
W-Modbus: Improved solar mode compatibility.
Added support for reading wireless network diagnostics over Modbus and BACnet.
Added support for the OEM Module Development Kit MK2.
Changed
Range test mode now automatically exits after 30 minutes.
Fixed
Fixed an issue that could cause failures when fetching network information via the mobile app.
Improved RS485 driver to prevent issues that could cause intermittent communication failures on the bus.
Fixed an issue that could cause some BACnet devices to not show up when doing discovery while using an IP to MS/TP router.
Known issues
While the W-BACnet/W-Modbus mobile app is connected to a W-BACnet/W-Modbus device, the device bandwidth is temporarily reduced by 33%.
Downgrading the firmware to a version below 3.0.0 will factory reset the device.
4.2.2
Released on 2026-05-28.
Added
Added firmware support for replacement of broken gateway through the mobile app.
Fixed
Fixed a bug that caused the boot time of the device to increase.
Fixed an issue that could cause communication to get stuck in solar mode.
Fixed a bug that caused app mode to briefly be 0 when read through SPI/UART before rebooting after
decommissioning
Known issues
While the W-BACnet/W-Modbus mobile app is connected to a W-BACnet/W-Modbus device, the device bandwidth is temporarily reduced by 33%.
Downgrading the firmware to a version below 3.0.0 will factory reset the device.
4.2.1
Released on 2026-03-16.
Added
Firmware support for commissioning W-BACnet and W-Modbus networks via the mobile app.
Firmware support for device identification in the mobile app.
Firmware support for switching to Solar mode for W-Modbus in the mobile app.
Added SPI/UART register and SPI interrupt for checking if a device was pinged by the mobile app.
Changed
LEDs are turned on by default for commissioning GW.
LEDs will no longer turn off after 30 minutes if there is any issue indication on the status LED.
Nodes in commissioning mode (except OEM modules) will now always advertise on BLE.
Fixed
Improved RS485 driver to prevent issues in edge cases.
Fixed a bug with specific controllers which could cause the RS485 status LED to be green, even though the received data was invalid.
Known issues
While the W-BACnet/W-Modbus mobile app is connected to a W-BACnet/W-Modbus device, the device bandwidth is temporarily reduced by 33%.
Downgrading the firmware to a version below 3.0.0 will factory reset the device.
4.2.0
Internal release.
4.1.1
Released on 2025-12-16.
Fixed
W-BACnet: Fixed issue where padded frames were not being handled correctly, causing
communication issues with some devices.
W-Modbus: Fixed intermittent issue with certain read requests in solar configurations.
Intermittent issue with devices causing an extra reboot during startup fixed.
Known issues
When manually uncommissioning a device through the push button, the device will restart
several times, which increases boot time slightly.
W-BACnet: when upgrading from any FW version less than 4.0.0, to this version
or above, there may be service disruption only during the time in which the FW
is being propagated to the rest of the nodes in a network.
When running W-BACnet version 4.1.0, padded frames are not handled correctly,
which may cause communication issues with some devices. This is fixed in version 4.1.1.
While the W-BACnet/W-Modbus mobile app is connected to a W-BACnet/W-Modbus device,
the device bandwidth is temporarily reduced by 33%.
Downgrading the firmware to a version below 3.0.0 will factory reset the device.
4.1.0
Released on 2025-11-07.
Added
W-BACnet: Improved network stability and performance on large networks / during high network load.
W-Modbus: GW's RS485 LED blinks green when there is valid RS485 traffic, red when there is invalid traffic and remains off when there is no traffic.
Changed
W-BACnet: Reduced the amount of Poll For Master frames sent on the local bus.
W-BACnet: Autobaud will now keep running until a device is found.
W-Modbus: Improved compatibility with Solar inverters / Smart Meters.
W-Modbus: Blink the RS485 RX LED only when valid traffic is received by the GW.
Fixed
Fixed intermittent RS485 framing issues on baudrates >= 76800.
Fixed bug where stop bit and parity setting was not correctly applied on boot in some cases.
Fixed bug where mobile app could still connect to device after the 3 minute timer had expired.
W-Modbus: Fixed bug which could cause unnecessary device scanning in some cases.
Known issues
W-BACnet: when upgrading from any FW version less than 4.0.0, to this version
or above, there may be service disruption only during the time in which the FW
is being propagated to the rest of the nodes in a network.
While the W-BACnet/W-Modbus mobile app is connected to a W-BACnet/W-Modbus device,
the device bandwidth is temporarily reduced by 33%.
Downgrading the firmware to a version below 3.0.0 will factory reset the device.
4.0.0
Released on 2025-08-07.
Added
W-BACnet: Improved performance when transmitting large amounts of data.
Wall Mount & DIN rail: In case of any operating system crash, all three LED's
will become solid red after booting up again. This state can be cleared with a
push of the button, after which the LED behavior will return to normal.
Added support for the Compact form factor.
Changed
PDR of any node in the network map now takes into account the PDR of each
parent all the way to the gateway. This better represents end-to-end PDR.
Fixed
Updates to gateways via the W-BACnet/W-Modbus App propagate throughout
networks without having to restart the gateway.
Known issues
W-BACnet: when upgrading from any FW version less than 4.0.0, to this version
or above, there may be service disruption only during the time in which the FW
is being propagated to the rest of the nodes in a network.
While the W-BACnet/W-Modbus mobile app is connected to a W-BACnet/W-Modbus device,
the device bandwidth is temporarily reduced by 33%.
Downgrading the firmware to a version below 3.0.0 will factory reset the device.
3.3.2
Released on 2025-04-25.
Added
W-BACnet: Autobaud can now be enabled by switching on dip switch no. 4
(previously used for stop bits). The W-BACnet device, after booting, will
"lurk" on the MS/TP bus until the baudrate of a connected BACnet device is
identified. If the baudrate cannot be identified within 90 seconds, legacy
behavior will be resumed. Baudrates in the order that they are tested by
autobaud are: 76800, 38400, 19200, 9600, 57600, 115200.
OEM modules: Ability to switch between BACnet and Modbus via SPI and/or UART
management interface.
OEM modules: Ability to read and write device name through SPI and/or UART
management interface.
Fixed
When OEM module nodes are decommissioned by a connected gateway, the
commissioning bit is now correctly cleared.
Improved network recovery time significantly after updating the gateway.
Known issues
After updating a Gateway through the W-BACnet/W-Modbus App, the upgrade may
not propagate to devices in the network unless the gateway is restarted. Fixed
in 4.0.0.
3.3.1
Internal release, no changes to firmware.
3.3.0
Released on 2024-12-05.
Added
The BLE status, whether the device is advertising or not, can be read through SPI/UART interfaces on the OEM module.
The firmware version can be seen on the network map with the next mobile app version (coming soon).
Changed
BLE advertisements now run for 3 minutes, with an interval of 417.5 ms.
The network map now works in commissioning mode as well.
Stop bit and parity are no longer configurable for the W-BACnet products.
GW always advertises for 1 minute after DFU update.
Fixed
The OEM documentation is updated.
Miscellaneous bug fixes.
SPI is now reset if SPI master device is reset.
RS-485 frame spacing is now more consistent.
Known issues
Pro form factor logos are wrong in the app.
3.2.7
Released on 2024-10-01.
Added
Rewrite I-Am, I-Have, and I-Am-Router-To-Network from broadcast to unicast to reduce the risk of broadcast storms, for W-BACnet products.
Fixed
Intermittent RS-485 bus communication issues fixed for W-BACnet products.
Known Issues
Pro form factor logos are wrong in the app.
3.2.5
Released on 2024-05-24.
Fixed
Consecutive responses to Modbus polls by client fixed.
3.2.4
Released on 2024-05-17.
Fixed
Intermittent mesh network loop issues fixed.
Rare wireless communication issues fixed.
Known Issues
Two consecutive Modbus responses can be put on the bus.
3.2.3
Released on 2024-04-30.
Fixed
Frequent changes in RS-485 bus parameters bug fixed.
3.2.0
Released on 2024-02-14.
Added
UART interface added as an alternative to SPI, can be used to control the oem modules.
A new app mode, APP_MODE_IDLE, has been added for the OEM modules, pausing any networking activity when in effect.
Changed
BLE version has been downgraded from 5 to 4 (see below concerning the App)
Fixed
All Apple iOS 17 devices are now able to use the W-Modbus app with W-Modbus devices on version 3.2.0 or later.
3.1.1
Released on 2023-12-18.
Changed
W-Modbus module documentation has been revised.
Known Issues
The W-Modbus app can only set device names with 8 characters of length or less on the home screen. Network map devices can have names up to 19 characters.
3.1.0
Released on 2023-11-28.
Added
SPI command added for rescanning Modbus addresses, for the oem modules.
SPI command added for BLE advertising, for the oem modules.
Fixed
Documentation for Modbus SPI button rescanning is fixed.
3.0.0
Released on 2023-10-27.
Added
DFU FOTA added, allowing firmware upgrades of an entire network by just upgrading the gateway.
Changed
Restricted Modbus addresses 248 through 255 will now also be scanned for compatibility with the solar industry products.
Fixed
Issue with detection of consecutive addresses on the Pro units fixed.
SPI NOP command no longer causes subsequent commands to time out on the oem module.
2.2.3
Released on 2023-08-23.
Fixed
Compatibility added for W-Modbus devices to work with solar inverters.
2.2.1
Released on 2023-04-27.
Added
Wall Mount and DIN rail LEDs can be turned on/off permanently by 5s button press.
Wall Mount and DIN rail LEDs can now indicate firmware version by 15s button press.
Pressing the button on the GW can turn on the LEDs on all wireless devices (Wall Mounts and DIN rails) in the network.
Changed
RS-485 reliability significantly improved.
LED colors behavior is updated.
Mode and network status is now combined and shown at the top LED.
GW's top LED is now magenta.
For mesh nodes, the network status LED indicates the connection quality: red for poor, yellow for fair, and green for good.
For mesh nodes, the network status LED blinking yellow signifies searching for a network to join.
RS-485 bus activity is shown on the middle LED, with blue/ green blinking for TX/ RX.
2.2.0
Released on 2023-03-24.
Added
W-BACnet and W-Modbus DIN rail products released.
2.1.1
Released on 2022-09-20.
Changed
Start token passing on the gateway when an MSTP device is connected to one of the nodes in the network.
2.1.0
Released on 2022-06-01.
Added
W-BACnet OEM Module released.
2.0.1
Released on 2022-05-05.
Fixed
W-Modbus Pro shows when at least one Modbus RTU server device address has been found.
W-Modbus Pro units will always find the lowest four RTU server device addresses present if more than four devices are on the same bus.
2.0.0
Released on 2022-04-25.
Added
W-BACnet Wall Mount product released.
1.2.0
Released on 2022-04-14.
Added
W-Modbus and W-Modbus Pro OEM Module products released.
Rescanning Modbus RTU addresses can be triggered by pushing button twice.
OEM module's app mode defaults to Mesh node from None.
Fixed
Missing address 247 while scanning for W-Modbus fixed.
1.1.2
Released on 2021-09-27.
Changed
RS-485 reliability improved.
Fixed
DIP switch bug fixed.
1.1.0
Released on 2021-06-29.
Added
SPI interface added for controlling the oem module.
New LED behavior: All LEDs will flash yellow when a node is scheduled to restart.
1.0.2
Released on 2021-06-01.
Fixed
Uncommissioning triggered by a short push on the push button is fixed.
1.0.0
Released on 2021-04-09.
Added
W-Modbus Wall Mount product released.
Warranty and Support
This section provides information about the warranty and support options available for W-BACnet products. It includes details on the warranty coverage, how to obtain support, and contact information for customer service.
Warranty Terms
The length of the warranty is a negotiation question between distributor and LumenRadio. Each distributor has a different term.
The warranty term is typically between 1-5 years from day of shipment, but you will need to check with your distributor to find out what applies to you.
The warranty or service agreement will be deemed void if:
The product is repaired, modified, or changed, unless such repair, modification or change has been approved by LumenRadio AB; or
The serial number on the product has been made illegible or is missing.
Return and complaint policy
The customer is required to examine the goods as soon as possible upon
receipt. If there is reason to believe that a product defect may result
in damage, a written complaint must be made immediately. LumenRadio's
liability shall pertain solely to defects that the customer asserts in
writing within 15 days after the defect is discovered or should have
been discovered, and no later than within the period stated in the agreement with LumenRadio from the invoice date.
When to Contact Support
Contact support for your W-BACnet product when:
The issue remains after you have checked your design against Hardware Integration and the Known Compatibility Issues, such as modules not joining the network, or unreliable BACnet communication.
You need advice on design verification, production testing or compliance testing of your product.
Who to contact
Contact your installer or distributor first for help with installation, wiring, power supply, or system configuration, and for suspected hardware faults or warranty questions.
Contact LumenRadio support for firmware errors or product issues that remain unresolved after troubleshooting or assistance from your installer or distributor.
How to submit a support ticket
Select Create Support Ticket in the manual's navigation, enter your contact details, a subject, and the information listed in [What to include in support request](#What to include in support request), then select Create Ticket. This opens the LumenRadio support portal in a new tab; complete and submit the request there, adding any relevant attachments.
If Create Support Ticket is unavailable or the new tab does not open, open the LumenRadio support portal directly and submit the same information. If you cannot access the portal, ask your installer or distributor to raise the request on your behalf.
What to include in support request
In order to get help as fast as possible, please include as much
information about your case as possible, including
The symptoms you are seeing
The product name, form factor, and serial number of each affected W-BACnet unit
The firmware version of each affected unit
The make and model of the connected BACnet controller/client and other connected devices
The troubleshooting steps you have already attempted and the result of each step
The schematics and PCB layout of the carrier board, and pictures of the product
The values read from the management interface, such as APP_MODE, NETWORK_STATUS and RS485_CONFIG
The power supply design of the carrier board
Serial bus settings (baudrate, parity, stopbits and if you are using autobaud or not)
Information about wireless conditions, distance between nodes and any obstructions.
If any external antenna is used.
{{#NOTE}}The more information you can provide, the faster we can help you.{{/NOTE}}
RMA claims
You can find the warranty terms for LumenRadio products in the Warranty and Support section.
If you have a claim that you believe is covered by the warranty, please submit an RMA claim via our {{action:open-rma:support system}}.
The RMA ticket must contain the serial number of the products,
a clear description of the observed fault, and details of how the
device has been installed.
Compliance Information
The available certifications for the W-BACnet module can be found on the W-BACnet support page.
FCC Information
FCC Information to User
This product does not contain any user-serviceable components and must only be used with approved antennas. Any product changes or modifications invalidate all applicable regulatory certifications and approvals.
FCC Guidelines for Human Exposure
This equipment complies with the FCC radiation exposure limits set forth for an uncontrolled environment. This equipment should be installed and operated with a minimum distance of 20 cm between the radiator and your body. This transmitter must not be co-located or operated in conjunction with any other antenna or transmitter.
FCC Declaration of Conformity
We, LumenRadio AB, Johan Willins gata 6, 416 64 Gothenburg, Sweden, declare under our sole responsibility that 840-2211 and 840-2215 W-BACnet comply with Part 15 of the FCC Rules. Operation is subject to the following two conditions:
This device may not cause harmful interference.
This device must accept any interference received, including interference that may cause undesired operation.
FCC Radio Frequency Interference Warnings and Instructions
This equipment has been tested and found to comply with the limits for a Class B digital device, pursuant to Part 15 of the FCC Rules. These limits are designed to provide reasonable protection against harmful interference in a residential installation. This equipment uses and can radiate radio frequency energy and, if not installed and used in accordance with the instructions, may cause harmful interference to radio communications. However, there is no guarantee that interference will not occur in a particular installation. If this equipment does cause harmful interference to radio or television reception, which can be determined by turning the equipment off and on, the user is encouraged to try to correct the interference by one or more of the following measures:
Reorient or relocate the receiving antenna.
Increase the separation between the equipment and the receiver.
Connect the equipment into an outlet on a circuit different from that to which the receiver is connected.
Consult the dealer or an experienced radio/TV technician for help.
Modifications made to the product, unless expressly approved by LumenRadio AB, could void the user's right to operate the equipment.
Industry Canada Statement
This digital apparatus does not exceed the Class B limits for radio noise emissions from digital apparatus set out in the Radio Interference Regulations of the Canadian Department of Communications.
Le présent appareil numérique n'émet pas de bruits radioélectriques dépassant les limites applicables aux appareils numériques de la classe B prescrites dans le Règlement sur le brouillage radioélectrique édicté par le ministère des Communications du Canada.
CE Declaration
840-2211 and 840-2215 W-BACnet comply with the Essential Requirements of the RED (Radio Equipment Directive) of the European Union (2014/53/EU). W-BACnet meets the ETSI EN 300 328 V2.2.2 conformance standards for radio performance.
Compliance Marking
FCC and Industry Canada Marking
The W-BACnet module is FCC certified as a single-modular transmitter.
The W-BACnet module is an FCC-certified radio module that carries a "Modular" grant. W-BACnet radio modules comply with the "Intentional Radiator" portion (Part 15C) of the FCC certification: Part 15.247 transmitter tests.
An end product that incorporates a W-BACnet module does not require additional testing or authorization for the W-BACnet transmitter. Host end products can use the FCC ID of the certified module as the FCC ID of the host end product. A label displaying the FCC ID of the W-BACnet module must be affixed and visible on the host end product for approval.
FCC IDs are required for host end products with radio transmitters.
Other Compliance
As the product manufacturer, you are responsible for ensuring that all compliance testing required by other local regulations (CE, UL, CSA, SRRC, C-Tick and so on) is completed. LumenRadio is happy to advise on compliance testing; contact LumenRadio support for details.
Cybersecurity Compliance
Cybersecurity overview
The W-BACnet OEM module is a radio module that you integrate into your own host product. It runs the same firmware and the same MiraMesh wireless network stack as the other W-BACnet products, and has been designed with security in mind: wireless communication is encrypted, the module has no IP interface, it is configured only by the host product, and firmware updates are signed and verified on every device.
This section describes the security design of the W-BACnet module, how it relates to the cybersecurity requirements of the EU Radio Equipment Directive (RED), and what you, as the manufacturer of the host product, are responsible for.
Lets the host product configure the wireless mesh network settings and monitor the module
Wired, local interface to the host product only. No IP.
Wireless mesh (MiraMesh, 2.4 GHz)
Carries BACnet traffic and firmware updates between W-BACnet devices
AES-128 encrypted. IPv6 used internally within the mesh only.
Bluetooth Low Energy (BLE)
Used by the W-BACnet mobile app for the network map and firmware updates, and by nRF Connect in bootloader mode
Disabled by default. Enabled only by the host product, through the management interface or the BOOTLOADER pin. Times out automatically.
MiraMesh uses IPv6 addressing internally between W-BACnet devices. This IP layer stays inside the encrypted mesh. The W-BACnet module has no Ethernet, Wi-Fi or other interface to an external IP network, no border-router function, and no cloud or remote management interface. It cannot be addressed or reached from the internet, and no IP services are exposed to users, integrators or the host product.
Security features
Encrypted wireless communication
All data sent over the W-BACnet wireless network is encrypted with AES-128. Only devices that have the network credentials can join the mesh. A network communicates securely using encryption once the gateway has been set to Secure Gateway mode, as the last step of Commissioning.
No external IP connectivity
IPv6 is used only for internal addressing within the mesh. The W-BACnet module does not route traffic to or from an external IP network.
Configuration controlled by the host product
The wireless mesh network settings of the W-BACnet module, such as the app mode used for commissioning, the RS485 configuration, resets and Bluetooth, are configured over the SPI or UART pins of its management interface. This is a wired connection to the host product, and the host product decides when and how these settings are read and changed.
It is the OEM vendor's responsibility to design the host product with security in mind: expose only non-sensitive items remotely, and require physical access to the host product for writing parameters to the module. See Responsibilities of the host product manufacturer.
The module does not advertise over BLE by default. The host product makes the module connectable to the W-BACnet app by setting BLUETOOTH_ENABLED in the SPI or UART management interface. The module then advertises for 3 minutes. If no connection is made within that time, advertising stops.
The module only enters bootloader (DFU) mode when the host product sets BOOTLOADER_ENABLED, or drives the BOOTLOADER pin low during a reset. It returns to application mode after 2 minutes without BLE activity.
Secure firmware updates
Firmware updates are sent from the W-BACnet mobile app over BLE to a gateway module. The gateway then distributes the update to the nodes over the W-BACnet mesh network. This happens in the background while normal BACnet communication continues, so the network keeps working during the update. A module can also be updated with nRF Connect while it is in bootloader mode. See Firmware Update.
The update process protects firmware as follows:
Encrypted distribution: within the mesh, the firmware package is sent as AES-128-encrypted messages, like all other mesh traffic.
Signed and verified on every device: each firmware file is digitally signed. The gateway and each node check the signature on the firmware they receive before installing it. The signature is also checked when a module is updated with nRF Connect in bootloader mode.
Rejected if invalid: if the signature check fails on any device, that device rejects the update and keeps running its current firmware.
Because an update can only start over BLE, and BLE and bootloader mode can only be enabled by the host product, firmware cannot be updated from the internet or over the BACnet interface.
Protection of sensitive data
Network keys and other credentials are not shared by default. When keys do need to be shared, for example when adding a device to an existing network, they are sent as encrypted blobs that only W-BACnet devices can decrypt. The mobile app and any intermediate device or connection only handle the encrypted blob, never the key in plain text. All other sensitive data, such as configuration, is also encrypted when sent wirelessly.
No remote management
The W-BACnet module cannot be configured, managed or updated from the internet or over the BACnet interface. Only the host product can configure it, through the SPI or UART management interface.
Read-only gateway diagnostics
When the host product sets a diagnostics address with DIAGNOSTICS_ADDRESS in the SPI or UART management interface, a module running in gateway mode acts as a BACnet server device and exposes wireless diagnostic objects, such as signal quality and network status, to the BACnet client. These objects are read-only: they cannot be written, and no configuration or control of the W-BACnet network is possible through them. The diagnostic objects contain only radio and network data and no personal data. Diagnostics are only available in gateway mode, and are disabled when DIAGNOSTICS_ADDRESS is 0.
EU Radio Equipment Directive – Article 3(3)(d), (e), (f)
Delegated Regulation (EU) 2022/30 applies cybersecurity requirements under RED Article 3(3)(d), (e) and (f) to certain radio equipment. The harmonized standards for these requirements are EN 18031-1, EN 18031-2 and EN 18031-3.
Requirement
Applies to
W-BACnet module
Art. 3(3)(d) – Network protection (EN 18031-1)
Internet-connected radio equipment
Not applicable. See below.
Art. 3(3)(e) – Personal data and privacy (EN 18031-2)
Internet-connected equipment processing personal data, toys, childcare equipment, wearables
Not applicable. The W-BACnet module does not process personal data.
Art. 3(3)(f) – Protection from fraud (EN 18031-3)
Equipment that can transfer money or virtual currency
Not applicable. The W-BACnet module has no financial functions.
Article 3(3)(d): the W-BACnet module has no interface to any external IP network and cannot communicate over the internet. IPv6 is used only for internal addressing within the encrypted MiraMesh network. Externally, the module carries BACnet frames over RS485 and is configured by the host product over SPI or UART. The module exposes no IP interface to the host product either, so it cannot connect to the internet in any form, even through the OEM's own product. If the host product has its own internet connection, the host product is the internet-facing equipment and is responsible for network protection on the IP side.
LumenRadio has therefore assessed the W-BACnet module as outside the scope of RED Article 3(3)(d). No Notified Body evaluation against EN 18031-1 is required. The W-BACnet module still includes security measures in line with the intent of EN 18031-1, including encrypted communication, host-controlled configuration, encrypted key sharing and signed firmware updates verified on every device, as described above.
Responsibilities of the host product manufacturer
The W-BACnet module is designed to be as secure as the wired BACnet network it replaces. The overall security of the end product and the installation also depends on the host product. As the manufacturer of the host product, you should:
Design the host product with security in mind. The wireless mesh network settings of the module can be configured over its SPI or UART pins, so the security of these settings depends on how the host product uses the management interface.
Expose only non-sensitive items remotely. If the host product offers remote access, expose only non-sensitive items, such as status and diagnostics, and protect the remote access with proper access control, strong passwords and up-to-date software.
Require physical access for write parameters. Writing parameters to the module, such as changing the app mode, resetting it, or enabling Bluetooth or bootloader mode, should require physical access to the host product.
Enable Bluetooth and bootloader mode only when needed. For example, enable them only after a local action on the host product, and do not make the BOOTLOADER and nRESET pins accessible from outside the product.
Complete commissioning. Set the gateway to Secure Gateway mode when commissioning is finished, so that the network communicates securely using encryption.
Keep firmware up to date. Install W-BACnet firmware updates when they are released, and give your customers a way to do the same. Read the release notes for security-related changes.
Treat BACnet as unauthenticated. BACnet MS/TP has no built-in authentication. Any device on the network can read and write properties on other devices. Restrict who and what can reach the BACnet network.
Reporting security issues
To report a suspected security vulnerability in a LumenRadio product, submit a request through the LumenRadio support portal.
Please include the product name, firmware version and a description of the issue. Do not disclose the vulnerability publicly until LumenRadio has had the chance to investigate and respond.